4.
Reversing Valve (O-Active or B-Active) –
(Appears for
heat pump systems only)
Change between “o” (Cool-Active) and “b” (Heat-Active).
Press the or button to set reversing valve setting.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
3.
Compressor (1 or 2) –
(Appears for heat pump systems only)
Change between CP1 and CP2.
Select the correct heat pump system.
• 1 = Single compressor heat pump system.
• 2 = Two compressor heat pump system.
Press the or button to select.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
6.
1
st
Stage
Temperature Differential
(1°F to 3°F) (0.5°C to 1.5°C)
Set the number of degrees between your “setpoint” temperature
and your “turn on” temperature.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE
5.
Temperature Scale (F or C) –
Choose Fahrenheit or Celsius.
Press the or button to select.
Press the
SW6
button to advance to the next screen.
7.
2
nd
Stage
Temperature Differential
(1°F to 6°F) (0.5°C to 3.0°C)
Set the number of degrees between when stage 1 turns on
and when stage 2 turns on.
Press the or button to set differential value.
Press the
SW6
button to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
FILTER
DIFF
ROOM
SET
REMOTE