Parameters

Parameter

Description

Range

Default

Recommended

Line 

Voltage

Average phase to phase 
line voltage

190-600

208

Nameplate 

Voltage

Delay On 

Break

Amount of time between 
the load de-energizing and 
re-energizing

0-10 

minutes

.1 

minute

4 minutes**

Fault Inter-

rogation

Amount of time before 
the load de-energizes due 
to a non-critical fault*

0-15 

seconds

15 

seconds

7-8 seconds**

Over/Under 

Voltage

Maximum/minimum phase 
to phase average voltage, 
respectively

2-25%

20%

12-15%**

% Phase 

Unbalance

Amount of allowable 
voltage unbalance

2-20%

20%

4-5%**

Reset 

Mode

AUTO or number of 
times the load can be 
re-energized after a load 
side fault before a manual 
reset is necessary 

 Note: When monitoring 

line side only, the 
reset mode will 
always be AUTO

AUTO, 

0-10

AUTO

AUTO

Control 

Mode

With control mode set 
to OFF, the load will 
energize if no 3- phase 
fault conditions exist; 
with control mode ON, 
the load will energize if no 
fault conditions exist and 
control voltage is present 
at terminals 1 and 3 of 
the ICM450

ON

or

OFF

ON

Based on wiring

*  Non-critical faults are faults such as High/Low Voltage and Phase Unbalance. 

Critical faults, such as Phase Loss and Phase Reversal, have a fault 
interrogation of under 2 seconds and it is not user adjustable.

**  For best recommendations, consult manufacturer of equipment.

Summary of Contents for ICM450

Page 1: ...American made products plus wiring diagrams troubleshooting tips and more visit us at www icmcontrols com ICM 450 Programmable Three Phase Voltage Monitor with 25 Fault Memory Protects motors from pre...

Page 2: ...Parameters Installation of the ICM450 shall be performed by trained technicians only Adhere to all local and national electric codes Disconnect all power to the system before making any connections Ca...

Page 3: ...is optional unit may be used to monitor line side only Wire the contactor and optional control voltage monitoring as in Figures 2 and 3 below Note Load line wire must be rated for 3 phase voltage rati...

Page 4: ...hrough setup by pressing and releasing the SETUP button 4 When the last parameter has been set the phase average will be displayed and the Setup LED will automatically turn OFF Setting the Parameters...

Page 5: ...Mode AUTO or number of times the load can be re energized after a load side fault before a manual reset is necessary Note When monitoring line side only the reset mode will always be AUTO AUTO 0 10 A...

Page 6: ...nce setting if necessary Front Over Volt Average phase phase voltage exceeds the maximum percentage 1 Check system for over voltage cause 2 Increase the percent over voltage setting if necessary 3 Inc...

Page 7: ...the faults press and hold FAULT for more than 5 seconds Load will not de energize when control voltage is OFF Phase Avg Load LED On Control LED Off The control mode setting is OFF press SETUP to get t...

Page 8: ...r In order to permit the Seller to properly administer the warranty the Buyer shall 1 Notify the Seller promptly of any claim submitting date code information or any other pertinent data as requested...

Reviews: