ICM Controls ICM450 Installation, Operation & Application Manual Download Page 2

Specification

Phase Unbalance Protection

• 

Voltage Unbalance:

 2-20% adjustable

Over/Under Voltage Protection

• 

Under Voltage:

 2-25% adjustable

• 

Over Voltage:

 2-25% adjustable

Phase Loss Protection

• 

Phase Loss Condition:

 Equals 25% of nominal for any given phase; system  

will shut down and a fault will be recorded should this occur

Delay on Break Timer

• 

Control Voltage:

 18-240 VAC

• 

Time Delay:

 0 to 10 minutes adjustable

Fault Interrogation Delay

• 

Time Delay:

 0 to 15 seconds adjustable

• Provides a delay between fault detection and system shutdown - helps to 

eliminate nuisance trips or unnecessary shutdowns

Parameters

Installation of the ICM450 shall be performed by trained technicians only. 

Adhere to all local and national electric codes. 
Disconnect all power to the system before making any connections.

Caution

Input

• 

Line Voltage:

 Universal, 190-630 VAC

• 

Frequency:

 50-60 Hz

• 

Load Side Monitoring:

 Optional

• 

Control Voltage:

 18-240 VAC

• 

Frequency:

 50-60 Hz

Output

• 

Type:

 Relay, SPDT

• 

Voltage Range:

 240VAC @ 10A maximum

• 

Frequency:

 50-60 Hz

Control Operating Temperature

• 

Operating Temperature:

 -40ºF to +167ºF (-40ºC to +75ºC)

• 

Storage Temperature:

 -40ºF to +185ºF (-40ºC to +80ºC)

LCD Operating Temperature

• 

Operating Temperature:

 -4ºF to +167ºF (-20ºC to +75ºC)

Mechanical

• 

Mounting:

 Surface mount using (2) #8 screws

• 

Terminations:

 Screw terminals

• 

Weight:

 12 ounces (341 grams)

Dimensions 

• 6 1/2” L, 4 1/4” W, 1 3/8” H   (16.5 cm. L, 10.8 cm. W, 3.5 cm. H)

Summary of Contents for ICM450

Page 1: ...American made products plus wiring diagrams troubleshooting tips and more visit us at www icmcontrols com ICM 450 Programmable Three Phase Voltage Monitor with 25 Fault Memory Protects motors from pre...

Page 2: ...Parameters Installation of the ICM450 shall be performed by trained technicians only Adhere to all local and national electric codes Disconnect all power to the system before making any connections Ca...

Page 3: ...is optional unit may be used to monitor line side only Wire the contactor and optional control voltage monitoring as in Figures 2 and 3 below Note Load line wire must be rated for 3 phase voltage rati...

Page 4: ...hrough setup by pressing and releasing the SETUP button 4 When the last parameter has been set the phase average will be displayed and the Setup LED will automatically turn OFF Setting the Parameters...

Page 5: ...Mode AUTO or number of times the load can be re energized after a load side fault before a manual reset is necessary Note When monitoring line side only the reset mode will always be AUTO AUTO 0 10 A...

Page 6: ...nce setting if necessary Front Over Volt Average phase phase voltage exceeds the maximum percentage 1 Check system for over voltage cause 2 Increase the percent over voltage setting if necessary 3 Inc...

Page 7: ...the faults press and hold FAULT for more than 5 seconds Load will not de energize when control voltage is OFF Phase Avg Load LED On Control LED Off The control mode setting is OFF press SETUP to get t...

Page 8: ...r In order to permit the Seller to properly administer the warranty the Buyer shall 1 Notify the Seller promptly of any claim submitting date code information or any other pertinent data as requested...

Reviews: