Specification
Phase Unbalance Protection
•
Voltage Unbalance:
2-20% adjustable
Over/Under Voltage Protection
•
Under Voltage:
2-25% adjustable
•
Over Voltage:
2-25% adjustable
Phase Loss Protection
•
Phase Loss Condition:
Equals 25% of nominal for any given phase; system
will shut down and a fault will be recorded should this occur
Delay on Break Timer
•
Control Voltage:
18-240 VAC
•
Time Delay:
0 to 10 minutes adjustable
Fault Interrogation Delay
•
Time Delay:
0 to 15 seconds adjustable
• Provides a delay between fault detection and system shutdown - helps to
eliminate nuisance trips or unnecessary shutdowns
Parameters
Installation of the ICM450 shall be performed by trained technicians only.
Adhere to all local and national electric codes.
Disconnect all power to the system before making any connections.
Caution
Input
•
Line Voltage:
Universal, 190-630 VAC
•
Frequency:
50-60 Hz
•
Load Side Monitoring:
Optional
•
Control Voltage:
18-240 VAC
•
Frequency:
50-60 Hz
Output
•
Type:
Relay, SPDT
•
Voltage Range:
240VAC @ 10A maximum
•
Frequency:
50-60 Hz
Control Operating Temperature
•
Operating Temperature:
-40ºF to +167ºF (-40ºC to +75ºC)
•
Storage Temperature:
-40ºF to +185ºF (-40ºC to +80ºC)
LCD Operating Temperature
•
Operating Temperature:
-4ºF to +167ºF (-20ºC to +75ºC)
Mechanical
•
Mounting:
Surface mount using (2) #8 screws
•
Terminations:
Screw terminals
•
Weight:
12 ounces (341 grams)
Dimensions
• 6 1/2” L, 4 1/4” W, 1 3/8” H (16.5 cm. L, 10.8 cm. W, 3.5 cm. H)