Installation
12
HANDLING
CODEX GT
Boilers are equipped with fittings for lifting operations and, in any case,they must be carefully moved with equipment
suitable for their dimensions and weights.
a
ATTENTION
The Personal Protective Equipment required by current legislation must be used.
INSTALLATION ROOM
The room where
CODEX GT
Boilers are to be installed must be exclusively used for them, compliant with the Technical Standards
and the Law in force and equipped with adequately dimensioned vents.
The spaces around the Boiler and towards the ceiling must be suitable for:
–
installing the appliance
–
reaching the safety devices
–
maintenance
–
repairing any breakage
–
opening the door of the installed burner, considering its opening direction (towards the right or the left).
A (*)
P4
≤90°
NO!
(*) A ≥ P4 (see “Size and fittings*)
a
ATTENTION
–
Consider the spaces necessary to access the adjustment and safety devices and to perform maintenance in compliance
with the legislation in force in the place of installation.
–
If the burner is fed with gas of specific weight greater than that of the air, the electrical parts must be positioned at least
500 mm from the ground.
m
IMPORTANT
COMBUSTION AIR:
CODEX GT
Boilers MUST be installed in rooms which are permanently vented with adequately
dimensioned vents, according to the appliance’s thermal power, and which comply with the Technical Standards and
the national and local Laws in force at the place of installation.