
Discharge Line Temperature Above 150°F (66°C) at End of
Freeze Cycle:
Ice machines that are operating normally will have
consistent discharge line temperatures above 150°F (66°C).
Verify the expansion valve sensing bulb is positioned and
secured correctly.
Discharge Line Temperature Below 150°F (66°C) at End of
Freeze Cycle
Ice machines that have a flooding expansion valve will
have a discharge line temperature that decreases each
cycle.
Verify the expansion valve sensing bulb is 100% insulated
and sealed airtight. Condenser air contacting an incorrectly
insulated sensing bulb will cause overfeeding of the
expansion valve.
10
1
Summary of Contents for IC-0170A
Page 1: ...Undercounter Ice Machines Technician s Handbook Revision Date 1 24 22...
Page 2: ......
Page 14: ...THIS PAGE INTENTIONALLY LEFT BLANK...
Page 17: ...16 How to Read a Serial Number Full Serial Number...
Page 154: ...WU 0100 WIRING DIAGRAM Self Contained Air cooled 153...
Page 155: ...IC 0170 IU 0170 IC 0220 IU 0220 WIRING DIAGRAM Self Contained Air cooled 154...
Page 156: ...Printed Circuit Bards PCB WU 0100 PCB 155...
Page 161: ...SPACE FOR TECHNICIAN S NOTES...
Page 162: ...SPACE FOR TECHNICIAN S NOTES...
Page 163: ...SPACE FOR TECHNICIAN S NOTES...
Page 164: ...SPACE FOR TECHNICIAN S NOTES...
Page 165: ......