Installation guide 

NP800R 

Date : 01/2012 

Print :23/08/2012 

Sheet : 

3

 

Issue : a 

 

 

Generalities 

 

For your safety, we recommend you to read the following information’s carefully. They have the aim to specify 
the essential precautions to the good installation and the correct operation of the devices. 
 

  Safety instructions 

1.1

The terminal blocks of the devices are studied to ensure the safety of the people during the operation of the 
devices. 
 
During installation, commissioning or maintenance, they can however present high voltages and possibly a 
thermal heating. Consequently, the following precautions must be followed: 
 

 

 

Connection of the terminal blocks at installation must be carried out after having ensured of the 

absence of any voltage 

 

Their access during operation must be carried out through adequate means ensuring as well electric 

as thermal insulation 

 

The connection of the earth (terminal T1-1) must imperatively be done with mean of a 2.5 mm² wire. 

 
 

Before powering the devices, it will be necessary to check in particular: 

 

 

The value of the voltage rating of the auxiliary supply and its polarization 

 

The good realization of connections 

 

Integrity of the connection to the earth. 

 

  Removal 

1.2

It is formally misadvised to withdraw the connectors with voltage or on load. 
The protective relay should never be open by the user. 
At their removal, it should completely isolate the protection of any external polarity and discharge capacitors 
by connecting the external terminals to ground. 
 

  Destruction of relays and recycling of packaging 

1.3

If necessary, the destruction of the relays will have to be carried out in accordance with the legislation in force, 
in particular in compliance with the environment and safety requirements. 
 
Ensure to re-use the cardboard box or otherwise insert it in a recycling circuit. The holds of transport in low 
density polyethylene are recyclable and should be valued by an appropriate circuit. 
 

  Relay failure 

1.4

The NP800R should in no case be opened by the User for repairs. In case of effective failure, the device must 
be shipped to the After Sales Dept. of ICE with all available information related to the detected fault.  

 

Summary of Contents for NP800R

Page 1: ...t is the sole property of ICE No duplication nor release to third party is allowed without prior authorization INSTALLATION GUIDE NP800R ICE 11 rue Marcel Sembat 94146 ALFORTVILLE CEDEX France TEL 33 01 41 79 76 00 FAX 33 01 41 79 76 01 E MAIL contact icelec com SITE WEB www groupeice com ...

Page 2: ...vided recommendations Before any use we recommend you to read the safety instructions of this installation guide This guide complements others document relating to the NP800R The Application guide which details the case of application of different protections and explicit their functions and settings The First handling guide which describes the data required for the commissioning and the operation...

Page 3: ...of the base Flush rear connection 9 3 1 3 3 Connection Flush rear connection 9 3 1 3 4 Put in place the protective relay Flush rear connection 9 3 2 Projecting rear connection case 10 3 2 1 Mounting and fixing Projecting rear connection case 11 3 2 2 Operation of replacement and connection Projecting rear connection case 12 3 2 2 1 Removal of relay 7000 or 700 Projecting rear connection case 12 3 ...

Page 4: ...ly be done with mean of a 2 5 mm wire Before powering the devices it will be necessary to check in particular The value of the voltage rating of the auxiliary supply and its polarization The good realization of connections Integrity of the connection to the earth Removal 1 2 It is formally misadvised to withdraw the connectors with voltage or on load The protective relay should never be open by th...

Page 5: ...e most recent technological advances ICE has developed the new NP800R range of digital protection relays to seamlessly replace the CEE 7000 and 700 series in modular cases The cases are identical to the CEE 7000 and 700 series avoiding cut out modifications Mechanical mounting Flush rear connection Projecting rear connection Projecting front connection Manufacturer Industrielle de Contrôle et d Eq...

Page 6: ...sity able to absorb shocks due to transport Storage 2 2 2 Storage Temperature 25 C to 70 C Unpacking 2 3 During extraction of NP800R of the box be careful to avoid shocks and not to distort the case Conduct an audit of the general appearance of the product before installation Consider making eliminate packaging through an appropriate recycling circuit Packaging 2 4 For packaging put the protective...

Page 7: ...7 For the measurement of currents and voltages Voltage s rated value 33V to 120V adjustable by the user Phase current s rated value 1A or 5A Earth current rated value 1A or 5A or link to a CBCT 0 2A Digital Inputs 2 8 NP800R is fitted with 4 digital inputs in case R2 or 8 digital inputs in case R3 Polarization voltage of digital inputs 20Vdc to 70Vdc for the auxiliary voltage range 19V to 70V 37Vd...

Page 8: ... NP800R Date 01 2012 Print 23 08 2012 Sheet 7 Issue a 3 NP800R case Flush rear connection case 3 1 Mechanical characteristics 3 1 1 R3 case R2 case Case Dimensions Width 125 mm Width 83 mm Height 172 mm Height 172 mm Depth 222 mm Depth 222mm Front Dimensions Width 140 mm Width 98 mm Height 217 mm Height 217 mm Weight Mass 4 5 kg Mass 3 5 kg ...

Page 9: ...HE R1 The protective relays NP800R are multifunctional and can replace many analogue relays In order to hide the location of old relays shutters in size R1 R2 and R3 are available KIT OBTU R1 KIT OBTU R2 KIT OBTU R3 The package includes the base kit a new base 4 mounting cradle screws additional connectors and the protective relay NP800R For details of size and mounting see the diagram 40037 Opera...

Page 10: ...ide of the relevant protective relay For the section of the wires to use see the User s guide of the relevant relay 3 1 3 4 Put in place the protective relay Flush rear connection Depending the type of protection place the strands of additional connectors out of the cutting of the base in order to not damage them during the insertion of the relay Insert the protective relay carefully in the mounti...

Page 11: ...ion Installation guide NP800R Date 01 2012 Print 23 08 2012 Sheet 10 Issue a Projecting rear connection case 3 2 R3 case R2 case Case dimension Width 125 mm Width 83 mm Height 172 mm Height 172 mm Depth 227 mm Depth 227mm Front dimension Width 125 mm Width 83 mm Height 172 mm Height 172 mm Weight Mass 4 5 kg Mass 3 5 kg ...

Page 12: ... 7010 The package includes the base kit a new base screws additional connectors and the protective relay NP800R The protective relays NP800R are multifunctional and can replace many analogue relays In order to hide the location of old relays blank covers in size R1 R2 and R3 are available Blank cover with mounting on the old base fixing short version R1 See drawing 801658 R2 See drawing 801659 R3 ...

Page 13: ...ut the 7000 or 700 relay Identify and disconnect the wires of the terminals Remove the base 3 2 2 2 Replacement of the base Projecting rear connection case Code pins to NP800R being different to relay 7000 and 700 the bases must be changed Check with the label Item 1 the good conformity between the base and the relay 3 2 2 3 Connection NP800R Projecting rear connection case Use the connection diag...

Page 14: ...ace the protective relay Projecting rear connection case Depending the type of protection place the strands of additional connectors out of the cutting of the base as not to damage them during the insertion of the relay Insert the protective relay carefully and plug it into the base Tighten the four fixing rods with a flathead screwdriver 3 5 mm Connect the additional connectors and block them wit...

Page 15: ...ion Installation guide NP800R Date 01 2012 Print 23 08 2012 Sheet 14 Issue a Projecting front connection case 3 3 R3 case R2 case Case dimension Width 125 mm Width 83 mm Height 172 mm Height 172 mm Depth 227 mm Depth 227mm Front dimension Width 125 mm Width 83 mm Height 172 mm Height 172 mm Weight Mass 4 5 kg Mass 3 5kg ...

Page 16: ...with projecting front connection case The package includes the base kit a new base screws additional connectors and the protective relay NP800R For dimension and fixing details see the drawing 40037 Operation of replacement and connection Projecting front connection case 3 3 2 3 3 2 1 Removal of relay 7000 or 700 Projecting front connection case Put out of service the electrical system in complian...

Page 17: ...in annex and the User guide of the relevant protective relay For the section of the wires to use see the User s guide of the relevant relay 3 3 2 4 Put in place the protective relay Projecting front connection case If rear clearance and depending the type of protection place the strands of additional connectors out of the cutting of the base in order to not damage them during the insertion of the ...

Page 18: ...relevant protective relay Annex 3 2 Reference of the connection diagram NP800R Type of protection Reference of diagram NPU800R S 39968 NPU800RE S 39973 NPUH800R S 39969 NPI800R S 39962 NPIH800R S 39964 NPID800R S 39963 NPIHD800R S 39965 NPG800R S 39961 NPW800R S 39970 NPM800R S 39966 NPM800RE S 39971 NPSC800R S 39967 NPM800RE S 39972 NP800R dimension and mounting diagram NP800 D 40037 BA800 dimens...

Reviews: