Instruction manual – AP901 Arc Protection Unit
38 (39
)
A1017B
12.8
M
ECHANICAL TESTS
Vibration test
2 ... 13.2 Hz ±3.5mm
13.2 ... 100Hz, ±1.0g
Shock/Bump test acc. to IEC 60255-
21-2
20g, 1000 bumps/dir.
12.9
C
ASING AND PACKAGE
Protection degree (front)
IP 50
Protection degree (back)
IP 20
Dimensions (W x H x D mm)
45 x 164 x 157mm
Weight
0.7kg
1.0 kg (with package)
12.10
E
NVIRONMENTAL CONDITIONS
Specified ambient service temp. range -35…+70°C
Transport and storage temp. range
-40…+70°C
Relative humidity
Up to 97%