Instruction manual – AP901 Arc Protection Unit
36 (39
)
A1017B
12
T
ECHNICAL DATA
12.1
P
ROTECTION
Trip time using mechanical trip relays
7ms*
Reset time (arc light stage)
2ms
Protection operational after power up
88ms
*total trip time using arc light (L>) or phase/residual overcurrent (I>) from AP910 and arc light (L>)
12.2
A
UXILIARY VOLTAGE
Us
80…265Vac/dc (option 18…72Vdc)
Maximum interruption
100ms
Maximum power consumption
5W
Standby current
90mA
12.3
T
RIP RELAYS
T1,
T2,
T3,
T4
Number
3 NO + 1 NC or 4 NO
Rated voltage
250V ac/dc
Continuous carry
5A
Make and carry for 0.5s
30A
Make and carry for 3s
16A
Breaking capacity DC, when time
constant L/R=40ms
40W;
0.36A at 110 Vdc
Contact material
AgNi 90/10
12.4
B
INARY
O
UTPUT
BO1
Rated voltage
+24V dc
Rated current
20mA (max)
Number of outputs
1