Instruction manual – AP901 Arc Protection Unit
23 (39
)
A1017B
6.3
C
IRCUIT BREAKER FAILURE PROTECTION
(CBFP)
AP901 includes a selective circuit breaker failure function which can be enabled by dipswitch
setting (see chapter 3.5). When enabled, the breaker failure function activates when the tripped
breaker fails to operate. Breaker failure function is activated if AP901 detects the presence of
light after a set operate time. When AP901 is set to operate on light and current both
parameters must persist to activate CBFP. Breaker failure can be set to operate either on
100ms or 150ms delay (see chapter 3.5).