4
Preservation Instructions
Unpacking Inspection
Caution: It is recommended using gloves and protective eyewear when unpacking
Verify product is as identified on the packing list. Air conditioner should arrive banded to pallet in the proper
upright position. See arrows on packaging for verification. Any evidence of damage should be noted on the freight
bill. The freight carriers claim procedure should be followed.
Ice Qube cannot accept responsibility for damages
that occur during shipping.
If the shipping container was damaged or marred in any way, check for scratches,
dents, loose hardware, presence of oil or any other irregularities with the Ice Qube TMS.
Package Contents
Included in the shipment with the air conditioner will be:
1.
Operation manual
2.
Mounting hardware
3.
Condenser air diverter plate
4.
Standard master warranty
5.
Ethernet controller manual (Optional)
6.
Enclosure gasket (Pre-installed)
Handling
Ice Qube recommends that the unit remains in the proper upright position, as indicated on the shipping container.
The unit must remain upright for a minimum of 24 hours before initial operation to ensure oil has returned to the
compressor. Operation before the 24-hour time may cause compressor damage and shorten the life of the system.
Operation before this 24-hour period will void all warranties.
Storage
The storage space temperature should be in the range of -40 to 85°C (-40 to 185°F) in a non-condensing
environment.
HAZARDOUS LOCATIONS MODELS ONLY
- CONDITIONS OF ACCEPTABILITY:
When installed in the end use equipment, the following considerations are to be examined:
1.
The maximum operating temperature of the devices while subjected to the temperature test at a 60°C
ambient air temperature is in accordance with the temperature class of the below table:
Maximum Temperature
T-Code
Unit
120°C
T4A
IQ1-2-3-4-5-6-8-10-12000EV
160°C
T3C
IQ14-17-20000EV
2.
The subject devices must be used within their Recognized “Ratings” and conditions of acceptability as
referenced in the User’s Manual.
3.
Consideration is to be given to the Conditions of Acceptability specified in the individual recognitions
when these components are employed in the end-use equipment.
Summary of Contents for Evolution Series
Page 7: ...7 Figure 1 Enclosure Installation Figure 2 Push to Connect Fitting Ambient Side Enclosure Side...
Page 9: ...9 Figure 4 Terminal Block Figure 5 Power Terminal Block...
Page 17: ...17 Schematic Wiring Diagrams Ordinary Locations 120V 220V 230V Figure 8 IQ350942 Rev A...
Page 18: ...18 Ordinary Locations 400V 460V 480V Figure 9 IQ350943 Rev A...
Page 19: ...19 Hazardous Locations 120V 220V 230V Figure 10 IQ350921 Rev A...
Page 20: ...20 Hazardous Locations 400V 460V 480V Figure 11 IQ350922 Rev A...
Page 21: ...21 Specification Drawing 1000EV Figure 12...
Page 22: ...22 2000EV Figure 13...
Page 23: ...23 3000EV Figure 14...
Page 24: ...24 4000EV Figure 15...
Page 25: ...25 5000EV Figure 16...
Page 26: ...26 6000EV Figure 17...
Page 27: ...27 8000EV Figure 18...
Page 28: ...28 10000EV Figure 19...
Page 29: ...29 12000EV Figure 20...
Page 30: ...30 14000EV Figure 21...
Page 31: ...31 17000EV Figure 22...
Page 32: ...32 20000EV Figure 23...
Page 40: ...40 Notes...