Ice Qube Evolution Series Operation And Installation Manual Download Page 11

 

11 

 

Operating Your System 

 

Once the Ice Qube TMS has been installed onto the enclosure and the power cable has been attached to a properly 
grounded electrical connection with adequate voltage and current supply, the unit is ready for operation. As soon as 
electrical power is supplied to the Ice Qube TMS, the cool air stream blower will start to operate. The blower will 
run continuously so that the controller can monitor the enclosure’s internal temperature. The enclosure temperature 
will be displayed on the face of the controller. 
 
If the enclosure temperature is greater than the factory cooling set-point of 80°F (27°C), the “Cool” status LED will 
flash. This indicates that the compressor’s automatic off cycle timer is working. The off cycle timer is factory set at 
3 ½ minutes. At the end of the 3 ½ minutes, the compressor and the condenser air blower will begin to operate and 
the cool LED will be steady. This signifies that the cooling system has begun operation to remove heat and humidity 
from the enclosure. The model may take 20 to 30 minutes before it achieves full capacity. 
 
If the heat load within the enclosure is less than the cooling capacity of the Ice Qube TMS, the temperature on the 
digital display will begin to decrease. When the temperature inside the enclosure decreases 7°F (4°C) below the 
“Cooling On” set-point, the compressor and condenser blower will cycle off. The cool air blower will continue to 
operate, circulating air within the enclosure. The controller has a factory programmed temperature differential of 7°F 
(4°C). Example: “Cooling On” @ 80°F (27°C); “Cooling Off” @ 73°F (23°C).

 

Ice Qube also offers an Internal Heat Output (IHO) which provides a heater located within the air conditioner for 
ordinary locations only. If the enclosure temperature is below the factory heating set-point of 50°F (10°C), the heat 
status LED will be lit. This indicates the heat relay has been energized and is providing power to the heater. There is 
no time delay before heating begins. When the temperature of the enclosure rises 7°F (4°C) above the set-point, the 
controller will de-energize the heat relay and cycle the heater off. 
 

Note: There is a dead band programmed into the controller that prevents heating and cooling from operating 
simultaneously. 
 
Note: See the label of the air conditioner for maximum wattage requirement of the heater. (Ord. Loc. only) 

Programming the Standard Controller 

 

The digital controller has many features that may or may not be required for all applications.  The controller has 
been programmed at the factory with typical default settings for immediate system operation.  
 
Please review the following default settings: 

1.

 

Cooling system on temperature 

 

 

80°F (27°C) 

2.

 

Heating system on temperature 

 

 

50°F (10°C); optional (Ord Loc Only) 

3.

 

High enclosure temperature alarm    

 

100°F (38°C) 

4.

 

Low enclosure temperature alarm   

 

40°F (4.4°C) 

5.

 

Audible and Visual alarm   

 

 

ON 

6.

 

Digital display in degrees   

 

 

Fahrenheit 

7.

 

Filter maintenance alarm   

 

 

0 days – Disabled 

8.

 

High condenser temperature alarm   

 

170°F (77°C) 

 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Evolution Series

Page 1: ...cations or Nonhazardous Locations OPERATION AND INSTALLATION MANUAL IMPORTANT PLEASE READ this manual and follow the instructions for safe and satisfactory installation and operation of this system Ke...

Page 2: ...er 14 Alarm Operation 14 Maintenance 15 Trouble Shooting 15 Schematic Wiring Diagrams 17 Ordinary Locations 17 120V 220V 230V 17 400V 460V 480V 18 Hazardous Locations 19 120V 220V 230V 19 400V 460V 48...

Page 3: ...thin the enclosure The three main thermal related systems that we employ are the closed loop cold air supply stream the heat rejection air stream and the vapor compression refrigeration system The clo...

Page 4: ...on as indicated on the shipping container The unit must remain upright for a minimum of 24 hours before initial operation to ensure oil has returned to the compressor Operation before the 24 hour time...

Page 5: ...rm air condenser blower will not operate if the room air temperature is below 80 F 27 C This is due to the fact that the programmable controller has a factory set point of 80 F 27 C The digital displa...

Page 6: ...Error Reference source not found and Error Reference source not found Mechanical Installation Instruction Caution Protective safety clothing such as helmet gloves and steel toe shoes are recommended...

Page 7: ...7 Figure 1 Enclosure Installation Figure 2 Push to Connect Fitting Ambient Side Enclosure Side...

Page 8: ...e Installation Checks 1 Check the air conditioner model label or specification for power requirements 2 Check the designated air conditioner power supply for adequate and proper electrical power requi...

Page 9: ...9 Figure 4 Terminal Block Figure 5 Power Terminal Block...

Page 10: ...ly Closed Red will be installed See Figure 6 Alarm Output Pre Installation Checks 1 Ensure that the power connected to the alarm wires is in an NEC approved Class 2 circuit 2 Check that alarm wire rou...

Page 11: ...ower will continue to operate circulating air within the enclosure The controller has a factory programmed temperature differential of 7 F 4 C Example Cooling On 80 F 27 C Cooling Off 73 F 23 C Ice Qu...

Page 12: ...ng until the enclosure temperature increases approximately 7 F 4 C Press 1 or 2 until the desired set point is displayed within a range of 0 F to 63 F 17 8 C to 17 C Notes Heat is only available with...

Page 13: ...will no longer flash and will show 4 To program the no PIN code mode press 2 and the display will show 0 indicating no PIN code With no PIN code pressing any button will permit access to the program...

Page 14: ...ature must fall 4 F 2 C before the alarm will reset The above alarms can be manually reset by entering the PIN code into the system 3 The filter day timer has expired The Alarm LED lights the display...

Page 15: ...d debris that may cause the system to fail The type of environment will determine the frequency of required maintenance Maintenance of the condensate management system will require access to the botto...

Page 16: ...ompressor and condenser warm air stream blower operating Yes No Is the enclosure door closed tightly Yes No Are all of the gaskets in place Yes No Has the condenser warm air stream filter been cleaned...

Page 17: ...17 Schematic Wiring Diagrams Ordinary Locations 120V 220V 230V Figure 8 IQ350942 Rev A...

Page 18: ...18 Ordinary Locations 400V 460V 480V Figure 9 IQ350943 Rev A...

Page 19: ...19 Hazardous Locations 120V 220V 230V Figure 10 IQ350921 Rev A...

Page 20: ...20 Hazardous Locations 400V 460V 480V Figure 11 IQ350922 Rev A...

Page 21: ...21 Specification Drawing 1000EV Figure 12...

Page 22: ...22 2000EV Figure 13...

Page 23: ...23 3000EV Figure 14...

Page 24: ...24 4000EV Figure 15...

Page 25: ...25 5000EV Figure 16...

Page 26: ...26 6000EV Figure 17...

Page 27: ...27 8000EV Figure 18...

Page 28: ...28 10000EV Figure 19...

Page 29: ...29 12000EV Figure 20...

Page 30: ...30 14000EV Figure 21...

Page 31: ...31 17000EV Figure 22...

Page 32: ...32 20000EV Figure 23...

Page 33: ...33 IQ1 2 3000EV Gasket and Cutout Same Gasket and Cutout for IQ1000EV IQ2000EV and IQ3000EV Figure 24...

Page 34: ...34 IQ4 5 6000EV Gasket and Cutout Same Gasket and Cutout for IQ4000EV IQ5000EV and IQ6000EV Figure 25...

Page 35: ...35 IQ8 10 12000EV Gasket and Cutout Same Gasket and Cutout for IQ8000EV IQ10000EV and IQ12000EV Figure 26...

Page 36: ...36 IQ14 17 20000EV Gasket and Cutout Same Gasket and Cutout for IQ14000EV IQ17000EV and IQ20000EV Figure 27...

Page 37: ...ARRANTY SET FORTH HEREIN IS STRICTLY LIMITED TO ITS TERMS AND IS IN LIEU OF ALL OTHER WARRANTIES GUARANTEES EXPRESS OR IMPLIED ARISING BY OPERATION OF LAW COURSE OF DEALING CUSTOM USAGE OF TRADE OR OT...

Page 38: ...om the date of shipment FCA from Ice Qube s facility in Greensburg Pennsylvania However such in field service is only available at the sole discretion of Ice Qube In field service may not be available...

Page 39: ...M IN FIELD SERVICE THESE UNITS WILL EITHER BE RETURNED TO THE FACTORY FOR REPAIR OR MAY BE ELIGIBLE FOR A REPLACEMENT UNIT THIS WILL BE AT THE SOLE DISCRETION OF ICE QUBE INC Extended Warranty Options...

Page 40: ...40 Notes...

Reviews: