 EF and EMF Series

 

 

 Installation Guidelines 

 Page 

 

Installation Guidelines 

 

For proper operation of the ICE-O-Matic ice machine, the following installation guidelines must be followed.  Failure to 
do so may result in loss of production capacity, premature part failures, and may void all warranties. 
 
Reference the installation parameters prior to installing the machine: 
 

Ambient Operating Temperatures 

Minimum Operating Temperature:  50°F  (10°C) 
Maximum Operating Temperature 100°F  (38°C), 110°F  (43°C) on 50 Hz. Models. 

Note: ICE-O-Matic icemakers and dispensers are not approved for outdoor installation. 

 

Incoming Water Supply 

(See Electrical and Plumbing Diagrams for line sizing) 

Minimum incoming water temperature:  40°F  (4.5°C) 
Maximum incoming water temperature:  100°F  (38°C) 
Minimum incoming water pressure:   20 psi  (1.4 bar) 
Maximum incoming water pressure:  60 psi  (4.1 bar)  

Note: If water pressure exceeds 60 psi (4.1 bar), a water pressure regulator must be installed. 
 
Drains  

All drain lines must be installed per local codes.  Flexible tubing is not recommended.  Route bin drain, float overflow 
drain and water condenser drain individually to a floor drain. 

 

The use of condensate pumps for draining water is not 

recommended by ICE-O-Matic.  ICE-O-Matic assumes no responsibility for improperly installed equipment. 
 

Water Filtration 

A water filter system should be installed with the ice machine. 
 

Clearance Requirements 

Self-contained air cooled ice machines must have a minimum of 6 inches (15cm) of clearance at the sides of the ice 
machine for proper air circulation. 
 

Stacking 

ICE-O-Matic flake ice machines are not designed to be stacked. 
 

Dispenser Application 

ICE-O-Matic flake ice machines are not designed for dispenser application. 
 

Electrical Specifications 

Refer to the serial plate at the rear of the ice machine to make sure proper voltage and circuit breaker size have been 
supplied.  Make sure the machine is on a dedicated circuit.  The EF and EMF Series Flakers are not supplied with an 
electrical power cord and will need to be installed and wired per local electrical codes. European installations require 
that the electrical supply fixed wiring must be provided with a disconnect means having a separation of at least 3mm in 
all poles. 
 

Adjustments 

Level the machine within 1/8 inch in all directions.  Adjust the cabinet or bin legs as required. 
Check the primary and secondary bin control for proper adjustment. 
Check the water level in the reservoir for proper adjustment. 
Check the safety control for proper adjustment. 
Check the water regulating valve adjustment if water cooled.  
 

Remote Machines 
Verify the ICE machine is compatible with the remote condenser.  Some ice machines and some remote 
condensers may or may not have a Mixing Valve (Head Master).  Only one valve is required per system. 
Kits are available to modify the condenser for compatibility.  For more information contact your ICE-O-Matic 
Distributor. 

Summary of Contents for Series 250 through 2306

Page 1: ...Installation Start Up and Maintenance Manual EF and EMF Flaked Ice Machines Series 250 through 2306 ICE O Matic 11100 East 45th Ave Denver Colorado 80239 Part Number 9081178 01 Date 1 06 Rev C...

Page 2: ...1...

Page 3: ...e Department E Mail Tech service iceomatic com Telephone Numbers Any Service communication must include 800 423 3367 All Departments Model Number 888 349 4423 Technical Assistance Only Serial number 3...

Page 4: ...Number and Serial Number Format Page 1 Installation Guidelines Page 2 3 Remote Condenser Guidelines Page 4 Electrical and Plumbing Requirements Page 6 How the Machine Works Page 9 Start Up Procedure...

Page 5: ...for carrier s inspection Visible Loss or Damage Any external evidence of loss or damage must be fully described and noted on your freight bill or express receipt and signed by the carrier s agent Cla...

Page 6: ...acts of God This warranty is valid only when installation service and preventive maintenance are performed by a Company authorized distributor a Company authorized service agency or a Company Regional...

Page 7: ...r Flaker Uses HFC Refrigerant This format is 14 characters long and begins with a date code followed by the ICE O Matic identifier and then a sequential number This is an entirely numerical serial num...

Page 8: ...ith the ice machine Clearance Requirements Self contained air cooled ice machines must have a minimum of 6 inches 15cm of clearance at the sides of the ice machine for proper air circulation Stacking...

Page 9: ...and fuse size according to the specifications listed on the serial data plate located on the rear of the ice machine cabinet 2 Supply power to the ice machine on a dedicated electrical circuit Only th...

Page 10: ...nduit The penetration should be within two feet of where the condenser will be located A roof jack must be installed at the penetration Installation Guidelines Ambient operating temperatures 20 F 28 9...

Page 11: ...ration Installation Guidelines Ambient operating temperatures 20 F 28 9 C to 120 F 48 9 C Condenser Airflow Condensers must have a vertical airflow ICE Machine Model Number Remote Condenser Model Numb...

Page 12: ...EF and EMF Series Electrical and Plumbing Requirements Page 6 Electrical and Plumbing Requirements 32 38 and 48 inch Cabinets SIDE VIEW REAR VIEW FRONT VIEW ICE O MATIC TOP VIEW...

Page 13: ...EF and EMF Series Electrical and Plumbing Requirements Page 7 Electrical and Plumbing Requirements EMF 400 800 1000 Air Water and Remote...

Page 14: ...EF and EMF Series Electrical and Plumbing Requirements Page 8 Electrical and Plumbing Requirements EMF2300 Air Water and Remote...

Page 15: ...r is delayed for 2 to 4 minutes After the compressor delay period the compressor and condenser fan motor air cooled machines only starts causing the temperature of the evaporator to drop The water in...

Page 16: ...l well at the bottom of the evaporator The Safety Control turns the machine off if the evaporator temperature reaches approximately 30 F 1C The Safety Control can be adjusted by turning the adjusting...

Page 17: ...ere will be a compressor delay of 2 to 4 minutes after turning the machine on If ice is touching the bin control thermal well for more than 3 minutes and the machine has not shut off turn the adjustin...

Page 18: ...rmed a minimum of every 6 months Local water conditions may require that cleaning be performed more often 2 Check the water level in the float reservoir 3 Clean the condenser air cooled machines to in...

Page 19: ...1 gallon 3 75l of approved U S FDA 21 CFR 178 1010 food equipment sanitizer to form a solution with 100 200 ppm free chlorine yield Reserve about 1 3 gallon for step 13 below 8 Turn the machine on an...

Page 20: ...er the thin layer on the surface of stainless steel that protects it from corrosion 3 Don t use cleaners that use chlorine or chlorides Don t use chlorine bleach or products like Comet to clean the st...

Page 21: ...all ice is out of the evaporator s 3 Place the ON OFF switch to the OFF position 4 Disconnect the tubing between the evaporator and float 5 Drain the water system completely 6 On water cooled machine...

Page 22: ...________________________________________________________________________________ __________________________________________________________________________________________ ____________________________...

Reviews: