EF and EMF Series

 

 

 

Remote Condenser Guidelines

 

 

Page 5 

Remote Condenser Installation 

 

The EMF1106R2 and EMF2306R2 remote ice makers incorporate the mixing valve in the condenser.  This 
configuration allows up to a 100 foot calculated remote line set run.  Reference the diagram below to calculate the 
maximum 100 foot line set run. 
 
For proper operation of the ICE-O-Matic ice machine, the following installation guidelines must be followed.  Failure to 
do so may result in loss of production capacity, premature part failure, and may void all warranties. 
 
Remote condensers must be installed per local building codes.  A two to four inch diameter roof penetration will be 
needed for refrigerant lines and electrical conduit.  The penetration should be within two feet of where the condenser 
will be located.  A roof jack must be installed at the penetration. 
 

Installation Guidelines 

 

Ambient operating temperatures:  -20°F (-28.9°C) to 120°F (48.9°C) 

 

Condenser Airflow: Condensers must have a vertical airflow.

   

 

 
ICE Machine Model Number 

 

 

 

Remote Condenser Model Number 

EMF1106R2 

      VRC1061 

EMF2306R2 

      VRC2061 

 

Limitations for new remote machines that have the headmaster mounted in the condenser. 

 

Maximum Rise is 35 feet. 
Maximum Drop is 15 feet. 

Airflow

Maximum equivalent run is 100 feet. 
 

Formula for figuring maximum equivalent run is as follows: 

 
Rise x 1.7 + Drop x 6.6 + horizontal run = equivalent run.  
 

 

 

          

Examples: 

35 ft. rise x 1.7 + 40 ft. horizontal = 99.5 equivalent feet line run 

 

 

 

        

 

 

 

 

 

 

 

 

 

 

 

 

 
 

  

 

 

 

 

 

 

 

 

 

 

 

 

34 ft. horizontal

10 ft. drop 

10 ft. drop x 6.6 + 34 ft horizontal = 100 
equivalent feet line run 

35 ft. rise 

40 ft. horizontal

Verify the ICE machine is compatible with the remote condenser.  
Some ice machines and some remote condensers may or may not 
have a Mixing Valve (Head Master).  Only one valve is required per 
system.  Kits are available to modify the condenser for compatibility.  
For more information contact your ICE-O-Matic Distributor. 

 

 
 
 

 

 

Summary of Contents for Series 250 through 2306

Page 1: ...Installation Start Up and Maintenance Manual EF and EMF Flaked Ice Machines Series 250 through 2306 ICE O Matic 11100 East 45th Ave Denver Colorado 80239 Part Number 9081178 01 Date 1 06 Rev C...

Page 2: ...1...

Page 3: ...e Department E Mail Tech service iceomatic com Telephone Numbers Any Service communication must include 800 423 3367 All Departments Model Number 888 349 4423 Technical Assistance Only Serial number 3...

Page 4: ...Number and Serial Number Format Page 1 Installation Guidelines Page 2 3 Remote Condenser Guidelines Page 4 Electrical and Plumbing Requirements Page 6 How the Machine Works Page 9 Start Up Procedure...

Page 5: ...for carrier s inspection Visible Loss or Damage Any external evidence of loss or damage must be fully described and noted on your freight bill or express receipt and signed by the carrier s agent Cla...

Page 6: ...acts of God This warranty is valid only when installation service and preventive maintenance are performed by a Company authorized distributor a Company authorized service agency or a Company Regional...

Page 7: ...r Flaker Uses HFC Refrigerant This format is 14 characters long and begins with a date code followed by the ICE O Matic identifier and then a sequential number This is an entirely numerical serial num...

Page 8: ...ith the ice machine Clearance Requirements Self contained air cooled ice machines must have a minimum of 6 inches 15cm of clearance at the sides of the ice machine for proper air circulation Stacking...

Page 9: ...and fuse size according to the specifications listed on the serial data plate located on the rear of the ice machine cabinet 2 Supply power to the ice machine on a dedicated electrical circuit Only th...

Page 10: ...nduit The penetration should be within two feet of where the condenser will be located A roof jack must be installed at the penetration Installation Guidelines Ambient operating temperatures 20 F 28 9...

Page 11: ...ration Installation Guidelines Ambient operating temperatures 20 F 28 9 C to 120 F 48 9 C Condenser Airflow Condensers must have a vertical airflow ICE Machine Model Number Remote Condenser Model Numb...

Page 12: ...EF and EMF Series Electrical and Plumbing Requirements Page 6 Electrical and Plumbing Requirements 32 38 and 48 inch Cabinets SIDE VIEW REAR VIEW FRONT VIEW ICE O MATIC TOP VIEW...

Page 13: ...EF and EMF Series Electrical and Plumbing Requirements Page 7 Electrical and Plumbing Requirements EMF 400 800 1000 Air Water and Remote...

Page 14: ...EF and EMF Series Electrical and Plumbing Requirements Page 8 Electrical and Plumbing Requirements EMF2300 Air Water and Remote...

Page 15: ...r is delayed for 2 to 4 minutes After the compressor delay period the compressor and condenser fan motor air cooled machines only starts causing the temperature of the evaporator to drop The water in...

Page 16: ...l well at the bottom of the evaporator The Safety Control turns the machine off if the evaporator temperature reaches approximately 30 F 1C The Safety Control can be adjusted by turning the adjusting...

Page 17: ...ere will be a compressor delay of 2 to 4 minutes after turning the machine on If ice is touching the bin control thermal well for more than 3 minutes and the machine has not shut off turn the adjustin...

Page 18: ...rmed a minimum of every 6 months Local water conditions may require that cleaning be performed more often 2 Check the water level in the float reservoir 3 Clean the condenser air cooled machines to in...

Page 19: ...1 gallon 3 75l of approved U S FDA 21 CFR 178 1010 food equipment sanitizer to form a solution with 100 200 ppm free chlorine yield Reserve about 1 3 gallon for step 13 below 8 Turn the machine on an...

Page 20: ...er the thin layer on the surface of stainless steel that protects it from corrosion 3 Don t use cleaners that use chlorine or chlorides Don t use chlorine bleach or products like Comet to clean the st...

Page 21: ...all ice is out of the evaporator s 3 Place the ON OFF switch to the OFF position 4 Disconnect the tubing between the evaporator and float 5 Drain the water system completely 6 On water cooled machine...

Page 22: ...________________________________________________________________________________ __________________________________________________________________________________________ ____________________________...

Reviews: