Remote Condenser
General Information
Page 6
The
RCA
remote condensers incorporate the mixing valve in the condenser. This configuration allows up to
a 100 foot calculated remote line set run. Reference the diagram below to calculate the maximum 100 foot
line set run.
The
RGA
remote condensers
Do Not
have a mixing valve in the condenser.
Maximum Rise is 35 feet
.
Maximum Drop is 15 feet.
Maximum equivalent run is 100 feet.
Formula for figuring maximum equivalent run is as follows:
Rise x 1.7 + Drop x 6.6 + horizontal run = equivalent run.
Examples:
35 ft. rise x 1.7 + 40 ft. horizontal = 99.5 equivalent feet line run
35 ft. rise
40 ft. horizontal
10 ft. drop x 6.6 + 34 ft horizontal = 100 equivalent feet line run
10 ft. drop
34 ft. horizontal
Airflow
Airflow