SYMPTON

POSSIBLE CAUSE SUGGESTED CORRECTION

Unit will not run

Blown fuse in P.C.Board

Replace fuse & check for cause of

No LED lighted-up

blown fuse

Master switch in OFF position

Turn switch to ON position

Inoperative P.C.Board

Replace P.C.Board

Loose electrical connections

Check wiring

Bin full yellow LED glows with

Inoperative or dirty ice level control

Replace or clean ice level control

no ice in the bin

Water yellow LED glows

Shortage or too soft water

See remedies for shortage of water
or install a mineral salt metering
device

Red-alarm LED glows

High head pressure

Dirty condenser. Clean
Inoperative fan motor. Replace

Ambient temperature too low

Move unit in warmer location

Reverse rotation yellow LED blinks

Too  hi  evap.  temperature

Check and charge refrigerant system

Shortage or lack of refrigerant

Reverse rotation yellow LED glows

Gear motor turns on reverse

Check gear motor capacitor

Too low gear motor rotating speed

Check rotor bearings, freezer
bearings and interior of freezer for
scores. Replace whatever worn or
damaged.

No rotation of gear motor

Check for power to drive motor
(16 A fuses)
Check for stator winding

Gear motor starts and stop

Check for correct operation of drive

after a while

motor magnetic sensor
Check for correct magnetic capacity
of magnetic cylinder

Water yellow LED and red LED

Inoperative Condenser Sensor

Replace it.

ON (steady) together

Water yellow LED and red LED

Inoperative Evaporator Sensor

Replace it.

blink together

Water yellow LED and red LED

Inoperative Ice Level Control

Replace it.

blink alternatively

Compressor cycles intermittently

Low voltage

Check circuit for overloading
Check voltage at the supply to the
building. If low, contact the power
company

Non-condensable gas in system

Purge the system

Compressor starting device with

Check for loose wires in starting
loose wires device

Low ice production

Capillary tube partially restricted

Blow charge, add new gas & drier,
after evacuating system with vacuum
pump

Moisture in the system

Same as above

Low water level in the freezer

Adjust to approx 20 mm below ice spout

Shortage of refrigerant

Check for leaks & recharge

Pitted or stained auger surface

Clean or replace auger

SERVICE DIAGNOSIS

Summary of Contents for ICEF 155

Page 1: ...Page 1 Page 1 SERVICE MANUAL ICE UNDERCOUNTER SERIES CUBER MODEL ICEF 155 Rev 07 2014...

Page 2: ...rain connections Final check list Installation practice OPERATING INSTRUCTIONS Start up Operational checks PRINCIPLE OF OPERATION How it works Water circuit Refrigerant circuit Mechanical system Opera...

Page 3: ...ak performance levels periodic maintenance checks must be carried out as indicated on page 29 of this manual Important operating requirements MIN MAX Air temperature 10 C 50 F 40 C 100 F Water tempera...

Page 4: ...NS Model Cond unit Finish Comp HP Ice bin cap Water req lt 24 HR ICEF 155 MACHINE SPECIFICATIONS Dimensions HEIGHT less legs 794 mm HEIGHT with legs 929 mm WIDTH 529 mm DEPTH 621 mm WEIGHT 51 Kg 230 5...

Page 5: ...nting pads 8 Use clean damp cloth to wipe the surfaces inside the storage bin and the outside of the cabinet 9 See data plate on the rear side of the unit and check that local main voltage corresponds...

Page 6: ...ter or conditioner WATERSUPPLY WATERCOOLEDMODELS The water cooled versions of Ice Makers require two separate inlet water supplies one for the water making the flaker ice and the other for the water c...

Page 7: ...Have the bin liner and cabinet been wiped clean 10 Has the owner user been given the User Manualandbeeninstructedontheimportanceof periodic maintenance checks G INSTALLATION PRACTICE 1 Hand shut off v...

Page 8: ...hardastheevaporating temperature has not yet reached the correct operating value It is necessary to allow the ice just made to cure itself and wait for about ten minutes for the evaporating tem peratu...

Page 9: ...SER TEMP EVAPORATOR TEMP ICE LEVEL CONTROL TRANSF T 40 50 C DATA PROCESSOR L N 11 10 9 1 2 7 8 6 5 4 3 13 12 FIG 3 2 1 L N COMPRESSOR 9 10 11 12 13 3 4 5 6 7 8 CONTACTOR COIL GEAR MOTOR FAN MOTOR ELEC...

Page 10: ...PERATION CHECKS UPON THE UNIT START UP D Removefrontservicepanelandifnecessary install the refrigerant service gauges on the corresponding Service valves to check both the HI and LO refrigerant pressu...

Page 11: ...of the flaker operations and the glowing of the YELLOW LED of shortage of water even though that water is indeed in the reservoir After this open the water supply line shutoff valve to fill up again t...

Page 12: ...ss of the two optical eyes are covered by a thin lay of scale To do it just follow the following procedure With unit OFF push and old the Reset Button of the PC Board Give power to the machine through...

Page 13: ...the ice level raises to interrupt the light beam running between the two infrared Leds the unit stops after six seconds with the simulteneous glowingofthe YELLOWLEDsignallingthe Full Bin situation NO...

Page 14: ...unit trips OFF again in alarm for 3 times in 3 hours the machine SHUTS OFF DEFINITIVELY After having eliminated the source of the excessive con densertemperature torestarttheicemachine it is necessary...

Page 15: ...4 5 6 7 8 CONTACTOR COIL GEAR MOTOR FAN MOTOR ELECTRONIC CARD RELAYS TRIAC RESET S E N S O R S WATER LEVEL GEAR MOTOR ROTATION CONDENSER TEMP EVAPORATOR TEMP ICE LEVEL CONTROL TRANSF DATA PROCESSOR L...

Page 16: ...em always check the type of refrigerant and quantity as specified on the individual ice machine dataplate Therefrigerantchargesindicatedarerelatives to averages operating conditions OPERATING PRESSURE...

Page 17: ...tage to the P C BOARD In case the condenser temperature sensor detects a temperature at the condenser lower than 1 C 33 F that signify that the ambient temperature is at the same value therefore it is...

Page 18: ...LED F P C BOARD Data processor The P C BOARD fitted in its plastic box located in the front of the unit consists of two separated printed circuits one at high and the other at low voltage and protecte...

Page 19: ...low to maintain a constant water level in the reservoir level that corresponds to the one in thefreezingcylindertoensurepropericeformation and fluidity On the inner side of the reservoir cover are fit...

Page 20: ...erefrigerant vaporcausingitstemperaturetoriseandbecome high pressure hot vapor which is then released through the discharge valve NOTE Itisveryimportanttomakesureofthe correct fitting of the cover on...

Page 21: ...ezertotheaccumulator to gain access to the sensor probe well and be able to pull out from this well the sensor probe 3 Trace the condenser sensor terminal plug blue on the left side of the control box...

Page 22: ...he machine stops with all LEDs blinking H REPLACEMENT OF THE ICE SPOUT 1 Remove the top panel 2 Slacken and remove the two metal straps that hold tight the polystyre insulations against the freezer up...

Page 23: ...e off from the auger bottom the upper half of the water seal NOTE Any time the auger is removed for replacement or inspection use extra care in handling the water seal parts so no dirt or foreignmatte...

Page 24: ...It is imperative to install a replace ment drier whenever the sealed refrigeration system is open Do not replace the drier until all other repairs or replacements have been completed 8 To install the...

Page 25: ...Page 25 Page 25 WIRING DIAGRAM AIR AND WATER COOLED 230 50 60 1...

Page 26: ...Page 26 Page 26...

Page 27: ...freezer for scores Replace whatever worn or damaged No rotation of gear motor Check for power to drive motor 16 A fuses Check for stator winding Gear motor starts and stop Check for correct operation...

Page 28: ...leaking Tighten screws holding the spout Excessive noise or chattering Mineral or scale deposit on auger Remove and manually polish auger and inner freezer walls and inner walls of freezer barrel usin...

Page 29: ...t temperature sensor 8 Check for water leaks and tighten drain line connections Pour water down bin drain line to be sure that drain line is open and clear 9 Check the ice level control sensor to test...

Page 30: ...heoverflow NOTE The ice made with the cleaning solution is slushy and coloured also it may tendtoloosefluiditycreatingsomeresistence in being elevated and extruded this situation canbeheardbythecreack...

Reviews: