Flake Ice Machines
Refrigeration System
Page
F6
To properly cool the condenser, there must be adequate airflow around the machine. The
ambient air temperature should not exceed 100
°
F (38
°
C). See Installation Guideline on
Page A6. The condenser coil and fan blades must be kept clean. The condenser can be
cleaned with compressed air or by using a brush.
If a brush is used, brush in the direction of the fins taking care not to bend or distort the
condenser fins. If the condenser fins are bent, this will also restrict the airflow through the
condenser and the fins will need to be straightened with a fin comb.
Water Cooled Condenser
If the machine has been installed properly, the water flow through the condenser will be
opposite the refrigerant flow. For proper water flow, the water for the condenser must be
piped through the water valve first. The water condenser must have a minimum of 20 PSI
(1.4 Bar) of flowing water pressure to the condenser. The water temperature to the
condenser must not exceed 100
°
F (38
°
C). A water regulating valve is used to control to flow
of water to the condenser. In areas that have poor water quality, the condenser may
eventually become coated with mineral deposits. This will decrease the efficiency of the
condenser resulting in high head pressure and high water usage. Water cooled condensers
replaced because of failure due to excessive mineral build up will not be covered under
warranty.
Water Regulating Valve
The water regulating valve controls the head pressure by regulating the
amount of water flow through the condenser. The bellows of the water
regulating valve are connected to the high side of the refrigeration system.
As the discharge pressure rises, the bellows expand, increasing the water
flow through the condenser. Adjusting the spring pressure screw at the top
of the valve can change the rate of water flow.
The unit should be run for 10 minutes, then the valve should be adjusted
as needed to maintain a refrigerant discharge pressure of 250 PSI (18.3
Bar). Water exiting the condenser should be between 100
°
F (38
°
C)
and110
°
F (43
°
C). When the machine is off, either on full bin or when the
selector switch is in the off position, the regulating valve will close
completely, stopping the flow of water through the condenser. If the water
flow does not stop when the machine is not running, the valve should be
replaced.
Air Cooled Condenser (Remote)
See Pages F10 or go to Page A10 for remote condenser installation.
High Pressure Safety
The high pressure safety control is a normally closed control. If the discharge pressure
becomes too high, the high pressure safety control will open and shut the machine off. The
high pressure safety control is an automatic reset type and will close and restart the machine
when the pressure drops. The high pressure safety control is used on all water cooled and
remote machines and some air cooled machines.
Summary of Contents for EF Series
Page 2: ......
Page 6: ......
Page 9: ...Flake Ice Machines General Information Page A7 EF Series ...
Page 10: ...Flake Ice Machines General Information Page A8 EMF Series ...
Page 11: ...Flake Ice Machines General Information Page A9 EMF Series 48 Inch Wide ...
Page 20: ...Flake Ice Machines Troubleshooting Trees Page C2 Machine Runs Does Not Make Ice ...
Page 21: ...Flake Ice Machines Troubleshooting Trees Page C3 Machine Runs Does Not Make Ice ...
Page 22: ...Flake Ice Machines Troubleshooting Trees Page C4 Machine Does Not Run ...
Page 23: ...Flake Ice Machines Troubleshooting Trees Page C5 Slow Production ...
Page 24: ...Flake Ice Machines Troubleshooting Trees Page C6 Low Production ...
Page 25: ...Flake Ice Machines Troubleshooting Trees Page C7 High Suction Pressure ...
Page 26: ...Flake Ice Machines Troubleshooting Trees Page C8 Machine Freezes Up Auger Seizes ...
Page 27: ...Flake Ice Machines Troubleshooting Trees Page C9 Auger Motor Amp Draw Fluctuates ...
Page 28: ...Flake Ice Machines Troubleshooting Trees Page C10 Water Leaking From Bottom of Evaporator ...
Page 29: ...Flake Ice Machines Troubleshooting Trees Page C11 Machine Produces Wet Ice ...
Page 31: ...Flake Ice Machines Troubleshooting Trees Page C13 Noise Coming from Evaporator ...
Page 41: ...Flake Ice Machines Drive System Page E8 Exploded View of the Evaporator ...
Page 43: ......
Page 46: ......
Page 61: ...Flake Ice Machines Electrical System Page G6 9071694 01 EF250 255 405 EF450A W ...
Page 62: ...Flake Ice Machines Electrical System Page G7 9071963 01 EF800A W ...
Page 63: ...Flake Ice Machines Electrical System Page G8 EMF450 405A W 9071958 01 ...
Page 64: ...Flake Ice Machines Electrical System G9 Page 9071954 01 EMF800A W ...
Page 65: ...Flake Ice Machines Electrical System Page G10 9071956 01 EMF705 1005 1006A W ...
Page 66: ...Flake Ice Machines Electrical System Page G11 9071962 01 EMF1106R ...
Page 67: ...Flake Ice Machines Electrical System Page G12 9071955 01 EMF2306A W ...
Page 68: ...Flake Ice Machines Electrical System Page G13 9071960 01 EMF2306R ...
Page 69: ...Flake Ice Machines Electrical System Page G14 9071959 01 EMF2305L ...
Page 70: ......
Page 71: ......
Page 72: ......