![ICE AIR VSHPW Operating And Maintenance Manual Download Page 5](http://html.mh-extra.com/html/ice-air/vshpw/vshpw_operating-and-maintenance-manual_610010005.webp)
5
Precautions and preparations listed are for general knowledge and to define basic guidelines. Local codes and existing practices should be observed and preformed by a professional.
Due to Ice Air’s ongoing product development programs, the information in this document is subject to change without notice.
1. Overview
The Ice Air model ELA-13086 is a digital thermostat with a TFT
touch screen user interface (thin film transistor liquid crystal display;
TFT-LCD). It provides the user with control of heating or cooling
mode, temperature adjustment, 7-day programmable schedule, and
various working mode options. A time clock and calendar are integral
functions to this device.
2. Main Features
• Adjustable fan speed: High, medium, low, and auto. (2-speed or
3-speed can be set by the dip switch; 2-speed is the default)
• Optional mode: cooling, heating, auto and fan only. (heating
function can be set by the dip switch; the default assumes a
heating function present)
• Clock can be set to 12-hour (AM/PM) or 24-hour mode
• Calendar ranges: from 2020 to 2099
• 7-day programmable schedule (optional, set by the dip switch,
the default is “function available.” If the user wants to disable
the “7-day programmable schedule” they can do so via the
dip switch, which would cause the thermostat to operate like a
simple thermostat)
• Time delay function: 3 minute delay for compressor at first
power-on; (this can be using the dip switch; the default is delay
post start-up)
• System failure warning
• Heating mode: Set the heating mode type (hydronic coil heater,
electric resistance, heat pump, etc.) using the dip switch
• Space temperature sensor is integral to the thermostat; the
temperature sensing range is: 32°F to 99°F
• Optional unit mounted temperature sensor: User can select the
integrated temperature sensor within the thermostat (default)
or the unit mounted temperature sensor. (range of temperature
detecting: 32°F to 99°F)
• Anti-freeze protection for hydronic heating applications
(protection triggered when return air temperature is less than
or equal to 40°F; thermostat returns to the previously set mode
when the ambient temperature is higher than 60°F)
• Cold air prevention function, available only for hydronic heating
applications in heating mode
3. Electrical Specifications
Power supply: AC24V/1A/50-60HZ
Warning input: AC24V±20%, keeping 10s (warning is triggered if
abnormal condition occurs for more than 10 seconds)
Rest output: AC24V
Control signal output: AC24V/0.5A
4. Outside Temperature Sensor
5K/3950K±1% (cable type)
5. Specification of TFT Screen
Size: 3.5”
Resolution: 320×480 dot RGB
Display area: 48.96(H) × 73.44(V) mm
Screen type: Capacitive TFT touch screen
Controls