Instance ID Object Name
Description
Units
Multiplier Definition Of Encoded Data
AI35
S4 Warning Level
Warning Setpoint for Sensor
4
PPM (96) 1.000000 40 to 990
AI36
S4 Alarm Level Alarm Setpoint for Sensor 4 PPM (96) 1.000000 50 to 1000
AI40
S5 Module State
Fault & Module State for
Sensor 5
No Units
(95)
1.000000
0 – Warm Up
Bit 0 – Normal
Bit 1 – Cal/Setup
Bit 2 – Factory
Bit 3 – Trouble
Bit 8 – Cal Sum
Bit 9 – Under Range
Bit 10 – Flow Loss
Bit 11 – Under Voltage
Bit 12 – Temperature
Bit 13 – Prog Cksum
Bit 14 – Lamp Fail
AI41
S5 Gas Number
Gas Number for Sensor 5
No Units
(95)
1.000000
0 to 44 (Refer to manual for
definition)
AI42
S5 Concentration
Gas Concentration for
Sensor 5
PPM (96) 1.000000 -20 to 1050
AI43
S5 Alarm State
Alarm State for Sensor 5
No Units
(95)
1.000000
0 - None
Bit 0 – Caution
Bit 1 – Warning
Bit 2 – Alarm
AI44
S5 Caution Level
Caution Setpoint for Sensor
5
PPM (96) 1.000000 30 to 980
AI45
S5 Warning Level
Warning Setpoint for Sensor
5
PPM (96) 1.000000 40 to 990
AI46
S5 Alarm Level Alarm Setpoint for Sensor 5 PPM (96) 1.000000 50 to 1000
AI50
S6 Module State
Fault & Module State for
Sensor 6
No Units
(95)
1.000000
0 – Warm Up
Bit 0 – Normal
Bit 1 – Cal/Setup
Bit 2 – Factory
Bit 3 – Trouble
Bit 8 – Cal Sum
Bit 9 – Under Range
Bit 10 – Flow Loss
Bit 11 – Under Voltage
Bit 12 – Temperature
Bit 13 – Prog Cksum
Bit 14 – Lamp Fail
AI51
S6 Gas Number
Gas Number for Sensor 6
No Units
(95)
1.000000
0 to 44 (Refer to manual for