Instance ID Object Name
Description
Units
Multiplier Definition Of Encoded Data
AI52
S6 Concentration
Gas Concentration for
Sensor 6
PPM (96) 1.000000 -20 to 1050
AI53
S6 Alarm State
Alarm State for Sensor 6
No Units
(95)
1.000000
0 - None
Bit 0 – Caution
Bit 1 – Warning
Bit 2 – Alarm
AI54
S6 Caution Level
Caution Setpoint for Sensor
6
PPM (96) 1.000000 30 to 980
AI55
S6 Warning Level
Warning Setpoint for Sensor
6
PPM (96) 1.000000 40 to 990
AI56
S6 Alarm Level Alarm Setpoint for Sensor 6 PPM (96) 1.000000 50 to 1000
AI60
S7 Module State
Fault & Module State for
Sensor 7
No Units
(95)
1.000000
0 – Warm Up
Bit 0 – Normal
Bit 1 – Cal/Setup
Bit 2 – Factory
Bit 3 – Trouble
Bit 8 – Cal Sum
Bit 9 – Under Range
Bit 10 – Flow Loss
Bit 11 – Under Voltage
Bit 12 – Temperature
Bit 13 – Prog Cksum
Bit 14 – Lamp Fail
AI61
S7 Gas Number
Gas Number for Sensor 7
No Units
(95)
1.000000
0 to 44 (Refer to manual for
definition)
AI62
S7 Concentration
Gas Concentration for
Sensor 7
PPM (96) 1.000000 -20 to 1050
AI63
S7 Alarm State
Alarm State for Sensor 7
No Units
(95)
1.000000
0 - None
Bit 0 – Caution
Bit 1 – Warning
Bit 2 – Alarm
AI64
S7 Caution Level
Caution Setpoint for Sensor
7
PPM (96) 1.000000 30 to 980
AI65
S7 Warning Level
Warning Setpoint for Sensor
7
PPM (96) 1.000000 40 to 990
AI66
S7 Alarm Level Alarm Setpoint for Sensor 7 PPM (96) 1.000000 50 to 1000
AI70
S7 Module State
Fault & Module State for
Sensor 8
No Units
(95)
1.000000
0 – Warm Up
Bit 0 – Normal
Bit 1 – Cal/Setup
Bit 2 – Factory
Bit 3 – Trouble
Bit 8 – Cal Sum
Bit 9 – Under Range
Bit 10 – Flow Loss
Bit 11 – Under Voltage
Bit 12 – Temperature
Bit 13 – Prog Cksum
Bit 14 – Lamp Fail
AI71
S8 Gas Number
Gas Number for Sensor 8
No Units
(95)
1.000000
0 to 44 (Refer to manual for
definition)
AI72
S8 Concentration
Gas Concentration for
Sensor 8
PPM (96) 1.000000 -20 to 1050