ICAS FIRE PANEL IFP–2.32

Button function 2 - ALARM RESET LOOP B

1

A+B at the same time

Enter into LEVEL 2

2

Press and hold B

LOOP B Choice

3

Hold B

1x A

+

1x LAMP

ALARM LOOP B Reset Choice

(Button LAMP is used at the end as 

confirmation of the action)

4

Release Buttons

FAULT LED is dark 

The table  

“Button function 3 – FAULT RESET”

 can be used step by step to delete fault 

manually in loops. Important! The fault of the loop has been fixed. In case that the Loop-fault 
has been removed, the Fault-Alarm is Reset automatically, or manually. 

1. First step for manual removing The Fault-Alarm is entering into LEVEL 2. – Press 

A+B at the same time – If received OK Signalization occurs (step 1).

2. Press and hold A (B) (step 2) 
3. Then hold A(B) and press 2x B(A) for Fault Reset Choice in the loop. The control 

choice can be checked by FAULT blinking LED. Do not release the button A(B). The 
control choice is confirmed by A(B)+Lamp button – If received OK Signalization 
occurs (step 3).

4. Release All buttons (step 4).

Button function 3 - FAULT Reset LOOP A

1

A+B at the same time

Enter into LEVEL 2

2

Press and hold A

LOOP A Choice

3

Hold A

2x B

+

1x LAMP

FAULT LOOP A Reset Choice

(Button LAMP is used at the end as 

confirmation of the action)

4

Release Buttons

FAULT LED is dark 

___________________________________________________________________________

ICAS AS

[email protected]

www.icas.no

7

Summary of Contents for IFP-2.32

Page 1: ...en control CHOR E detectors 9V detector can be connected only Alarm in one Alarm in all function The different functions are chosen by use of jumper The IFP 2 32 is supplied by 230V AC and the interna...

Page 2: ...r VD 04 shielded cable or equivalent type Shield of the cable has to be terminated in the 0V in all the Detectors and to Shield terminal in the Fire Panel Set all jumpers in correct position Switch th...

Page 3: ...SMOKE DETECTORS CONNECTION CHOR E SMOKE DETECTORS Connection meets EN52 2 with only the exception of clause 8 2 4 Removal of a point JUMPERFIX ________________________________________________________...

Page 4: ...detected when the loop is open or when the loop is shorted If the battery is very low and starts to be undercharged and main power is off the IFP 2 32 is switched off 3 LED SIGNALIZATION Power Dark N...

Page 5: ...evel 2 The actual Loop LED is lightning TEST At least one loop is in test mode Can be switched off on in level 2 Actual Loop LED is flashing OK SIGNALIZATION POWER LED 2x flashes and 2x short beeps Us...

Page 6: ...alarm in loops NOTE The detectors in the loop is not in alarm the current in the loop is lesser than 12 mA 1 First step is entering into LEVEL 2 Press A B at the same time If received OK Signalization...

Page 7: ...t Alarm is entering into LEVEL 2 Press A B at the same time If received OK Signalization occurs step 1 2 Press and hold A B step 2 3 Then hold A B and press 2x B A for Fault Reset Choice in the loop T...

Page 8: ...the loop The control choice can be checked by OFF blinking LED Do not release the button A B The control choice is confirmed by A B Lamp button If received OK Signalization occurs step 3 4 Release Al...

Page 9: ...tch Off On Test Choice of the loop The control choice can be checked by TEST blinking LED Do not release the button A B The control choice is confirmed by A B Lamp button If received OK Signalization...

Page 10: ...x LAMP LOOP B is in Test Off On Choice Button LAMP is used at the end as confirmation of the action 4 Release Buttons FAULT LED is dark 5 LAMP SIREN at the same time or wait 30 s Exit LEVEL 2 and retu...

Page 11: ...LT Reset A 3x pressed B for Switch Off On A 4x pressed B for Switch Test Off On LAMP SIREN Return into LEVEL1 A LAMP for confirmation previous choices A 1x pressed B for ALARM Reset A 2x presed B for...

Page 12: ...oltage 12 V 20 for CHOR E 9 5V 5 OUTPUTS Fault relay 1x 125VAC 0 5A 24VDC 1A Alarm relay 1x 125VAC 0 5A 24VDC 1A Transistor outputs OC 2x 14V 0 1A Power output for external device 12 V 20 5mA 9 5V 5 5...

Page 13: ...4 2007 A2 Control Unit for electrical fire alarm systems for buildings Power Supply for electrical fire alarm systems for buildings IFP 2 32 Optional requirements State Test Documentation IFP 2_32 Man...

Page 14: ...DANCE WITH THE MANUFACTURER S RECOMMENDATION ALWAYS USE SEALED LEAD ACID BATTERIES YUASA NP0 8 12 12V 0 8Ah LOOPS CHECKS Set the TEST function in IFP 2 32 for LOOP A and B For further instruction see...

Reviews: