ICAS FIRE PANEL IFP–2.32
Button function 2 - ALARM RESET LOOP B
1
A+B at the same time
Enter into LEVEL 2
2
Press and hold B
LOOP B Choice
3
Hold B
1x A
+
1x LAMP
ALARM LOOP B Reset Choice
(Button LAMP is used at the end as
confirmation of the action)
4
Release Buttons
FAULT LED is dark
The table
“Button function 3 – FAULT RESET”
can be used step by step to delete fault
manually in loops. Important! The fault of the loop has been fixed. In case that the Loop-fault
has been removed, the Fault-Alarm is Reset automatically, or manually.
1. First step for manual removing The Fault-Alarm is entering into LEVEL 2. – Press
A+B at the same time – If received OK Signalization occurs (step 1).
2. Press and hold A (B) (step 2)
3. Then hold A(B) and press 2x B(A) for Fault Reset Choice in the loop. The control
choice can be checked by FAULT blinking LED. Do not release the button A(B). The
control choice is confirmed by A(B)+Lamp button – If received OK Signalization
occurs (step 3).
4. Release All buttons (step 4).
Button function 3 - FAULT Reset LOOP A
1
A+B at the same time
Enter into LEVEL 2
2
Press and hold A
LOOP A Choice
3
Hold A
2x B
+
1x LAMP
FAULT LOOP A Reset Choice
(Button LAMP is used at the end as
confirmation of the action)
4
Release Buttons
FAULT LED is dark