VII. TABLE OF INDICATOR STATUS / TABEL STATUS INDIKATOR
LINE
INPUT
INVERTER
OUTPUT
BY
PASS
FAULT
OVER
LOAD
BUZZER
STATUS
CONDITION
RECOMMENDED
SOLUTION
ON ON - - -
- Normal
-
- ON -
-
-
Every 4
seconds
Utility power failure
-
- ON -
-
-
Every 1
second
Battery will
discharge completely
Close your software
and files in use
ON ON - - -
Every 4
seconds
Rectifier failure
Call for service
ON - ON
-
ON
Continuous
1. UPS not running
2. Overload
Remove some load
from the UPS
ON
-
ON
ON
-
Continuous
1. Inverter failure
Refer to trouble
shooting guide
VIII. TROUBLE SHOOTING / PETUNJUK KETIDAK NORMALAN
SYMPTOM PROBABLE
CAUSE
RECOMMENDED SOLUTION
1.
UPS not running
1.
Turn on the UPS
“INPUT” and “BYPASS”
indicator are “ON”
2.
Overload
1. Remove some load from the UPS
2. If it remains the same, call for service
“INPUT”, “BYPASS” and
“FAULT” indicator are “ON”
and alarm sounds continuously
Inverter failure
1.
Turn off main switch and turn on main
switch again
2.
If UPS doesn’t recover, call for service
“INPUT” indicator is “OFF”
and alarm sounds periodically
Utility power failure
1.
Check utility power is present at wall
outlet
2. Otherwise, call for service
No Output Voltage when input
power fails
Batteries discharged
completely
1. Recharging the battery by keep the main
switch “ON” for 10 hours
2. Retest the battery discharging again. If it
remains the same, call for service
“INPUT” and “INVERTER”
indicator are “ON” but alarm
sounds
Rectifier failure
Call for service