6
Site
wiring
fault
indicators
7
Battery
service
indicator
8
Battery
mode
indicator
9
General
alarm
indicator
Related
topics:
v
v
v
v
v
v
v
v
Mode
indicator
The
mode
indicator
1
shows
the
mode
of
the
uninterruptible
power
supply.
When
the
mode
indicator
is
steady
green,
the
uninterruptible
power
supply
is
in
normal
mode.
The
uninterruptible
power
supply
checks
and
charges
its
battery
as
necessary.
When
the
mode
indicator
is
flashing
green,
the
uninterruptible
power
supply
is
in
standby
mode.
Standby
mode
means
that
the
uninterruptible
power
supply
is
turned
off,
but
is
still
connected
to
the
main
power
source.
No
power
is
available
from
the
uninterruptible
power
supply
output
sockets.
When
the
mode
indicator
is
steady
red,
the
uninterruptible
power
supply
is
in
bypass
mode
because
of
one
of
the
following
conditions:
v
The
uninterruptible
power
supply
has
overheated
v
The
uninterruptible
power
supply
has
an
overload
condition
of
103%
through
110%
for
30
seconds
v
The
uninterruptible
power
supply
detects
a
fault
in
the
battery
or
in
the
uninterruptible
power
supply
electronics
assembly
When
the
mode
indicator
is
flashing
red
and
the
alarm
is
sounding,
the
voltage
range
alarm
setting
might
not
be
correct.
When
a
SAN
Volume
Controller
is
connected
to
the
uninterruptible
power
supply,
the
SAN
Volume
Controller
automatically
adjusts
the
voltage
range
settings.
Take
no
action
for
this
alarm
condition
unless
it
persists
for
more
than
five
minutes
after
a
SAN
Volume
Controller
has
been
connected
to
this
uninterruptible
power
supply
and
powered
on.
Related
topics:
v
On
button
Use
the
on
button
2
to
turn
on
the
main
power
to
the
uninterruptible
power
supply.
10
Installation
Guide
Summary of Contents for TotalStorage
Page 1: ...IBM TotalStorage SAN Volume Controller Installation Guide V ersion 1 2 0 SC26 7541 02...
Page 2: ......
Page 3: ...IBM TotalStorage SAN Volume Controller Installation Guide V ersion 1 2 0 SC26 7541 02...
Page 22: ...xx Installation Guide...
Page 36: ...14 Installation Guide...
Page 58: ...36 Installation Guide...
Page 74: ...52 Installation Guide...
Page 80: ...58 Installation Guide...
Page 84: ...62 Installation Guide...
Page 89: ......
Page 90: ...Part Number 64P8120 Printed in USA SC26 7541 02 1P P N 64P8120...
Page 91: ...Spine information IBM TotalStorage SAN Volume Controller Installation Guide Version 1 2 0...