When
the
drawer
power
cords
are
connected
to
the
dc
power
distribution
panel,
make
sure
there
is
less
than
1
ohm
resistance
between
the
drawer
frames
or
the
rack
frame.
DC
Rack
Power
Cables
The
customer
provides
the
power
cables
from
the
-48
V
dc
power
source
to
the
dc
power
distribution
panel.
The
-48
V
dc
rack
must
be
connected
to
a
-48
V
dc
power
source
that
is
electrically
isolated
from
the
ac
power
source.
In
addition,
the
-48
V
dc
power
source
must
be
reliably
grounded.
The
-48
V
dc
rack
may
be
connected
to
two
separate
-48
V
dc
power
sources.
When
the
rack
is
connected
to
two
power
sources,
both
power
sources
must
be
reliably
grounded.
Power
cables
used
in
the
United
States
and
Canada
are
listed
by
Underwriter’s
Laboratories
(UL)
and
certified
by
the
Canadian
Standards
Association
(CSA).
These
power
cables
have
the
following
characteristics:
v
Power
cables
and
ground
cables
must
be
a
minimum
of
6
AWG
stranded
copper
(or
equivalent)
for
lengths
up
to
50
feet
from
the
power
source.
v
All
connectors
must
be
the
copper
crimp
type
(compression).
Connector
metal
must
be
compatible
with
the
cable
metal.
12
7014
Model
T00,
and
Model
T42
Service
Guide
Summary of Contents for THINKPAD T42 -
Page 1: ...7014 Series Model T00 and Model T42 System Rack Service Guide SA38 0577 05 ERserver...
Page 2: ......
Page 3: ...7014 Series Model T00 and Model T42 System Rack Service Guide SA38 0577 05 ERserver...
Page 10: ...viii 7014 Model T00 and Model T42 Service Guide...
Page 36: ...24 7014 Model T00 and Model T42 Service Guide...
Page 72: ...60 7014 Model T00 and Model T42 Service Guide...
Page 80: ...68 7014 Model T00 and Model T42 Service Guide...
Page 85: ......