14. With the three required people (one person on each end and one person in the

middle), rotate the heat exchanger 90° and up onto the three rectangular
packing inserts.

15. With one person holding the heat exchanger steady on the package inserts,

have another person remove the inner and outer hose access panels. Push
the panels up and out to remove them. See 14. Set the hose access panels
aside.

16. Position one person on each end of the heat exchanger. Have each person

grasp and hold the under side of the heat exchanger with one hand and hold
the top of the heat exchanger with the other hand. Position the third person in
the middle of the heat exchanger and grasp the heat exchanger by the
handles. Have all three people carefully lift the heat exchanger and carry it to
the rear of the rack.

Outer hose
access panel

Inner hose
access panel

Figure 23. Rotating the heat exchanger 90° and removing the hose access panels

36

Rear Door Heat eXchanger V2: Installation and Maintenance Guide

Summary of Contents for Rear Door Heat eXchanger V2

Page 1: ...Rear Door Heat eXchanger V2 Type 1756 Installation and Maintenance Guide...

Page 2: ......

Page 3: ...Rear Door Heat eXchanger V2 Type 1756 Installation and Maintenance Guide...

Page 4: ...nd Environmental Notices and User Guide documents on the IBM Documentation CD and the Important Notices and Warranty Information documents that comes with the product Fourth Edition September 2013 Cop...

Page 5: ...ing the heat exchanger 30 Routing cables through the upper and lower air baffles 42 Front to rear cable channels and caps 43 Routing and securing the hoses 44 Raised floor environment 44 Raised floor...

Page 6: ...ent 84 Avis de conformit la r glementation d Industrie Canada 84 Australia and New Zealand Class A statement 84 European Union EMC Directive conformance statement 85 Germany Class A statement 85 VCCI...

Page 7: ...n Ennen kuin asennat t m n tuotteen lue turvaohjeet kohdasta Safety Information Avant d installer ce produit lisez les consignes de s curit Vor der Installation dieses Produkts die Sicherheitshinweise...

Page 8: ...anslations for that caution statement are in the IBM Rack Safety Information document under Statement 1 Be sure to read all caution and danger statements in this document before you perform the proced...

Page 9: ...power cords from devices in the rack cabinet into electrical outlets that are located near the rack cabinet and are easily accessible v Each rack cabinet might have more than one power cord Be sure to...

Page 10: ...structions in the rack documentation before you install devices remove devices or relocate the rack Statement 14 CAUTION Goggles are needed for the procedure L011 viii Rear Door Heat eXchanger V2 Inst...

Page 11: ...n which you install the heat exchanger can be on a raised floor or a non raised floor Each heat exchanger can remove 100 000 Btu per hour or approximately 30 000 watts of heat from your data center Se...

Page 12: ...e IBM Documentation CD The IBM Documentation CD contains documentation for your rack product in Portable Document Format PDF and includes the IBM Documentation Browser to help you find information qui...

Page 13: ...OK If you are using Red Hat Linux insert the CD into the CD or DVD drive then run the following command from the mnt cdrom directory sh runlinux sh Select your rack product from the Product menu The A...

Page 14: ...nvenient or problem situations v Attention These notices indicate potential damage to programs devices or data An attention notice is placed just before the instruction or situation in which damage mi...

Page 15: ...loops on page 14 v Providing a redundant secondary cooling loop water supply or enough room air conditioning to handle a tolerable heat load if the function of one or more of the heat exchangers is c...

Page 16: ...1 C 64 4 F 1 8 F for ASHRAE Class 1 Environment 22 C 1 C 71 6 F 1 8 F for ASHRAE Class 2 Environment Note See Heat exchanger performance for more information v Required water flow rate as measured at...

Page 17: ...performance of the heat exchanger 30 kW heat load As described in Water supply requirements for secondary loops on page 13 a given water temperature may be used only if the system that is supplying th...

Page 18: ...djust the water temperature accordingly Otherwise the water temperature must be above the maximum dew point allowed at that datacenter installation 140 130 120 110 100 90 80 70 60 50 heat removal as f...

Page 19: ...able 2 Installation and removal tools Tool Part to install or remove FRU part number Phillips screwdriver Hinge bracket air baffle 73G5363 8 mm socket Air baffle 73G1458 10 mm socket Hinge bracket 73G...

Page 20: ...heat exchangers designed for non IBM Enterprise racks Coolant distribution units 3 4 inch inside diameter hose kits Water treatment Chillers Raised floor grommets v Services Installation of door and s...

Page 21: ...oor Standing CD6 5 260 305 kW 400 V 480 V or 208 V Customers in locations other than Europe can contact Eaton Williams Group or Coolcentric see Miscellaneous parts and services supplier on page 10 htt...

Page 22: ...icle free deionized water or particle free distilled water with appropriate controls for avoiding these issues v Metal corrosion v Bacterial fouling v Scaling The water cannot originate from the prima...

Page 23: ...essing Environments Information about obtaining this document is at http www ashrae org publications page 1279 Search on Thermal Guidelines for Data Processing Environments Pressure The water pressure...

Page 24: ...px Search on document number iso 4126 1 v Be installed so that it is easily accessed for inspection maintenance and repair v Be connected as close as possible to the device that it is intended to prot...

Page 25: ...e Parker quick connect couplings that are used on the heat exchanger because of the excessive pressure drop associated with flowing through four quick connect pairs in series These must be very low ne...

Page 26: ...ure to specification Secondary side temperature feedback for controlled water temperature to specification Secondary side temperature feedback for controlled water temperature to specification Seconda...

Page 27: ...xible hoses maximum length 15 24 meters 50 feet Loop heat exchanger Supply CS CS CS CS CS Secondary side temperature feedback for controlled water temperature to specification Return Supply CS CS Shut...

Page 28: ...ature to specification Supplier built coolant distribution unit CDU suggested features Temperature and flow metering monitoring Leak detection or water level sensing and shutdown Local and remote moni...

Page 29: ...o be attached and the manifolds must match the capacity rating of the pumps and the loop heat exchanger between the secondary cooling loop and the building chilled water source Anchor or restrain all...

Page 30: ...shutoff valves for each supply and return line This provides a way to service or replace an individual heat exchanger without affecting the operation of other heat exchangers in the loop To ensure tha...

Page 31: ...Fluid Connectors quick connect couplings at one end which are attached to the heat exchanger and must either have a low impedance quick connect coupling or nothing so as to attach to a barb at the oth...

Page 32: ...on and support from IBM Integrated Technology Services If you would like to procure assistance with coordinating and managing the installation and support of the IBM Rear Door Heat eXchanger V2 Type 1...

Page 33: ...cument that comes with the rack or to download the document from the IBM website go to http www 947 ibm com support entry portal docdisplay lndocid migr 5091922 If the rack was unpacked without using...

Page 34: ...the rack down the ramp The other specially trained persons must guide the rack down the ramp by holding onto the rack frame Slowly roll the rack down the ramp until the casters are on the floor Move...

Page 35: ...d align the holes in the latch plate with the holes on the rack flange Secure the latch plate to the rack frame with the two screws Close the door and make sure that it latches securely Latch plate Sc...

Page 36: ...of the heat exchanger c Optional Secure the outer hose access panel to the heat exchanger with an M4 screw see Figure 14 d Reconnect power to the rack and all components then close and latch the heat...

Page 37: ...bracket rotate it 180 and screw the bracket to the rear door heat exchanger Shipping bracket Screw Figure 15 Reversing the shipping bracket Chapter 3 Special instructions if the heat exchanger comes...

Page 38: ...28 Rear Door Heat eXchanger V2 Installation and Maintenance Guide...

Page 39: ...s before you connect power to the rack or any of the installed components v Repair all leaks before you connect power to the rack or any of the installed components v After the heat exchanger is fille...

Page 40: ...tion that begins on page iii and Installation guidelines on page 29 2 Use the wrench that comes with the rack to lower the front and rear leveling pads Make sure that the rack is level to the floor 3...

Page 41: ...carton 6 Remove the parts and tools from the carton and set them near the rack Do not unpack the heat exchanger until later in the procedure Figure 17 Removing the cardboard top from the heat exchange...

Page 42: ...ck mounting flange of the rack b Align the holes in the latch plate with the holes in the flange and clip nuts then secure the latch plate in place with two M6 screws Screws M6 clip nuts Latch plate F...

Page 43: ...sure that the four screw holes in the bracket align with the four screw holes in the rack d Secure the bottom hinge bracket to the rack with four M6 screws Note Use a torque screwdriver to tighten the...

Page 44: ...to partially insert a screw in the hole that is the farthest away from the rear of the rack See the illustration Do not fully tighten the screw at this time d Rotate the hinge bracket to the left or r...

Page 45: ...he weight of this part or unit is between 32 and 55 kg 70 5 and 121 2 lb It takes three persons to safely lift this part or unit C010 Attention a Because of the size and weight of the heat exchanger t...

Page 46: ...16 Position one person on each end of the heat exchanger Have each person grasp and hold the under side of the heat exchanger with one hand and hold the top of the heat exchanger with the other hand P...

Page 47: ...r in an upright position See the illustration for the correct placement of hands for the three people who are required to lift and move the heat exchanger in an upright position Person 1 lift handles...

Page 48: ...ady have a third person climb the platform ladder rotate the top hinge bracket and position the top hinge bracket pin in the hole on the top of the heat exchanger 20 Align the two open holes in the to...

Page 49: ...the upper air baffle on the rack a Climb the platform ladder and loosen the two screws that secure the rear cable access cover and remove the cover b Secure the air baffle to the rack with three M6 s...

Page 50: ...freely 27 Attach the hoses and fill the heat exchanger with water See Routing and securing the hoses on page 44 and Filling the heat exchanger with water on page 48 for information about routing and...

Page 51: ...the outer hose access panel to the heat exchanger with an M4 screw see Figure 29 d Reconnect power to the rack and all components then close and latch the heat exchanger Outer hose access panel Option...

Page 52: ...d bundle hot air will escape from the open space in the air baffle The following illustration shows the correct way to bundle and route cables through the upper air baffle The following illustration s...

Page 53: ...the cap down so that it rests lightly on the cables This helps prevent hot air recirculation from the rear of the rack to the front of the rack If a cable channel is not used make sure that the cap is...

Page 54: ...m air baffles v Bundle signal cables together in a rectangle so that the air baffle sliders are closed as far as possible Do not bundle signal cables together in a circular formation For more informat...

Page 55: ...in wide Notes a Each hose must be routed through the access hole lengthwise so that the hose has the entire 200 mm 8 in to pass through the floor If adjacent racks share a hole in the floor increase t...

Page 56: ...on the valve trapped air from the hoses might have migrated to the heat exchanger To perform the air purging procedure complete step 7 on page 52 through step 10 on page 52 in Filling the heat exchang...

Page 57: ...and from the heat exchanger and will void the heat exchanger warranty If the hoses must be run overhead either route the hoses through the rack vertically or route them vertically down the hinge pivot...

Page 58: ...procedure L011 Attention Wear safety goggles or other eye protection whenever you fill drain or purge air or nitrogen from the heat exchanger 1 Remove the inner hose access panel from the inside of th...

Page 59: ...cap from the air purging valve Note The valve is similar to the valve on a bicycle or automobile tire Outer hose access panel Optional screw Figure 38 Removing the outer hose access panel Supply manif...

Page 60: ...Connect the return and supply hoses Note To avoid damage to cooling system tubing do not apply excessive force to the couplings Supply manifold coupling Female Supply hose assembly Male Return manifo...

Page 61: ...ect the supply hose complete the following steps a Align the male hose quick connect coupling with the female supply manifold coupling Note If you misalign the couplings or if the pressure has not bee...

Page 62: ...ector to the heat exchanger air purging valve If you connect the wrong end of the hose no water will flow 9 When there is a steady stream of water into the container from the air purging tool disconne...

Page 63: ...tom of the heat exchanger 13 Optional Secure the outer hose access panel to the heat exchanger with an M4 screw see Figure 43 Outer hose access panel Optional screw Figure 43 Installing the outer hose...

Page 64: ...54 Rear Door Heat eXchanger V2 Installation and Maintenance Guide...

Page 65: ...d all components before you connect or disconnect the water supply lines and drain or fill the heat exchanger The following illustration shows the locations of components on the heat exchanger Note Wh...

Page 66: ...exchanger complete the following steps 1 Shut off the flow of water at the source Depending on your facility this might mean turning off the pump unit closing a valve at the pump unit or a similar ac...

Page 67: ...hose and supply hose from the heat exchanger and move them out of the way Outer hose access panel Optional screw Figure 46 Removing the outer hose access panel Supply manifold coupling Female Supply h...

Page 68: ...ected 7 Place the drain end of the air purging tool into a container that can hold at least 11 4 liters 3 gallons of water Air purging valve Drain valve Figure 48 Removing the cap from the air purging...

Page 69: ...hose if filtered and oil free compressed air is available you can attach the compressed air hose to the air purging valve to force water out of the exchanger Keep the air pressure at 50 pounds per squ...

Page 70: ...ifficult to connect the hose b Pull the female collar back and move the couplings toward each other c Exert pressure until the female collar locks in place with an audible click Note After the couplin...

Page 71: ...er replaceable units CRUs Tier 1 CRU Replacement of Tier 1 CRUs is your responsibility If IBM installs a Tier 1 CRU at your request without a service contract you will be charged for the installation...

Page 72: ...r supply lines and drain or fill the heat exchanger Removing the heat exchanger To remove the heat exchanger complete the following steps 1 Read the safety information that begins on page iii and Inst...

Page 73: ...the outside of the heat exchanger If the optional screw is installed remove it See the following illustration Outer hose access panel Optional screw Figure 51 Removing the outer hose access panel Cha...

Page 74: ...es are needed for the procedure L011 Attention Make sure that proper handling procedures are followed when you work with any chemically treated water that is used in the rack cooling system Make sure...

Page 75: ...ain the valve caps from the air purging valve and from the drain valve Air purging valve Drain valve Figure 52 Removing the caps from the air purging valve and drain valve Chapter 5 Maintaining the he...

Page 76: ...depending on the amount of water that comes out of the hose v If only a little or no water comes out of the air purging tool the heat exchanger is sufficiently drained Go to step 8 on page 67 v If a s...

Page 77: ...the door has been drained 8 After making sure that the heat exchanger is drained complete the following steps a Remove the air purging tools if used b Screw the valve caps onto the air purging valve a...

Page 78: ...ar enough so that you can grasp the lift handles and lift the heat exchanger off the bottom hinge pin g Carefully lower the heat exchanger to the floor so that it rests on one corner 10 Position one p...

Page 79: ...hanger To install the replacement heat exchanger complete the following steps 1 Read the safety information that begins on page iii and Installation guidelines on page 29 2 Remove the cardboard top fr...

Page 80: ...rt or unit is between 32 and 55 kg 70 5 and 121 2 lb It takes three persons to safely lift this part or unit C010 Attention a Because of the size and weight of the heat exchanger three trained persons...

Page 81: ...ls aside 7 Position two people on each end of the heat exchanger Have each person grasp and hold the under side of the heat exchanger with one hand and hold the top of the heat exchanger with the othe...

Page 82: ...ght position See the illustration for the correct placement of hands for the three people who are required to lift and move the heat exchanger in an upright position Person 1 lift handles Person 2 lif...

Page 83: ...hile two people hold the heat exchanger steady have a third person climb the platform ladder rotate the top hinge bracket and position the top hinge bracket pin in the hole on the top of the heat exch...

Page 84: ...eriodically check that the rear door swings freely If necessary adjust the height of the right front leveler until the rear door does swing freely 16 Attach the hoses and fill the heat exchanger with...

Page 85: ...he outer hose access panel to the heat exchanger with an M4 screw see Figure 61 d Reconnect power to the rack and all components then close and latch the heat exchanger Outer hose access panel Optiona...

Page 86: ...latch with the hole on the outside of the door and from the inside secure the mounting bracket and the latch to the heat exchanger with the screw 4 When the heat exchanger is closed and latched make...

Page 87: ...roven compat us to make sure that the hardware and software is supported by your IBM product v Go to http www ibm com supportportal to check for information to help you solve the problem v Gather the...

Page 88: ...er information is http www ibm com systems bladecenter The address for IBM IntelliStation information is http www ibm com systems intellistation How to send Dynamic System Analysis data to IBM Use the...

Page 89: ...tp www ibm com partnerworld and click Find Business Partners on the right side of the page For IBM support telephone numbers see http www ibm com planetwide In the U S and Canada call 1 800 IBM SERV 1...

Page 90: ...80 Rear Door Heat eXchanger V2 Installation and Maintenance Guide...

Page 91: ...FOR A PARTICULAR PURPOSE Some states do not allow disclaimer of express or implied warranties in certain transactions therefore this statement may not apply to you This information could include techn...

Page 92: ...nel volume KB stands for 1024 bytes MB stands for 1 048 576 bytes and GB stands for 1 073 741 824 bytes When referring to hard disk drive capacity or communications volume MB stands for 1 000 000 byte...

Page 93: ...Limits Particulate v The room air must be continuously filtered with 40 atmospheric dust spot efficiency MERV 9 according to ASHRAE Standard 52 21 v Air that enters a data center must be filtered to...

Page 94: ...ruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required...

Page 95: ...kt entspricht den Schutzanforderungen der EU Richtlinie 2004 108 EG zur Angleichung der Rechtsvorschriften ber die elektromagnetische Vertr glichkeit in den EU Mitgliedsstaaten und h lt die Grenzwerte...

Page 96: ...71137 Ehningen Germany Telephone 49 7032 15 2937 Email tjahn de ibm com Generelle Informationen Das Ger t erf llt die Schutzanforderungen nach EN 55024 und EN 55022 Klasse A VCCI Class A statement Th...

Page 97: ...People s Republic of China Class A electronic emission statement Taiwan Class A compliance statement Appendix B Notices 87...

Page 98: ...88 Rear Door Heat eXchanger V2 Installation and Maintenance Guide...

Page 99: ...ing 56 fill 48 installation guidelines 29 installing 30 installing and removing 29 installing replacement 69 maintenance 55 parts and tools 9 performance 6 planning 5 purge 49 removing 62 67 replacing...

Page 100: ...outing and securing hoses in a raised floor environment 44 S Safety information v secondary cooling loop 13 air exposure 13 control and conditioning 12 coolant distribution unit 11 flexible hoses conn...

Page 101: ...website continued support line telephone numbers 79 Index 91...

Page 102: ...92 Rear Door Heat eXchanger V2 Installation and Maintenance Guide...

Page 103: ......

Page 104: ...Part Number 00D2434 Printed in USA 1P P N 00D2434...

Reviews: