Installation and User's Guide

Summary of Contents for 5595-1AX

Page 1: ...IBM Tower UPS T1 0kVA and T1 5kVA Installation and User s Guide...

Page 2: ......

Page 3: ...IBM Tower UPS T1 0kVA and T1 5kVA Installation and User s Guide...

Page 4: ...x C Notices on page 41 and read the IBM Safety Information and the IBM Systems Environmental Notices and User Guide on the IBM Documentation CD Copyright IBM Corporation 2014 US Government Users Restr...

Page 5: ...s 27 Removing the battery tray on tower models 27 Mounting the new battery pack 28 Chapter 7 Troubleshooting and maintenance 29 Alarms and faults 29 Service and support 30 Chapter 8 Parts listing 31 A...

Page 6: ...iv Installation and User s Guide...

Page 7: ...dukt Lees voordat u dit product installeert eerst de veiligheidsvoorschriften Ennen kuin asennat t m n tuotteen lue turvaohjeet kohdasta Safety Information Avant d installer ce produit lisez les consi...

Page 8: ...you identify potential unsafe conditions in an IBM product that you are working on Each IBM product as it was designed and manufactured has required safety items to protect users and service technici...

Page 9: ...Guidelines for servicing electrical equipment Observe these guidelines when you service electrical equipment v Check the area for electrical hazards such as moist floors nongrounded power extension co...

Page 10: ...unding of components such as power supplies pumps blowers fans and motor generators do not service these components outside of their normal operating locations v If an electrical accident occurs use c...

Page 11: ...L001 DANGER Hazardous voltage current or energy levels are present inside any component that has this label attached Do not open any cover or barrier that contains this label L001 Safety ix...

Page 12: ...to properly wired outlets v When possible use one hand only to connect or disconnect signal cables v Never turn on any equipment when there is evidence of fire water or structural damage v Disconnect...

Page 13: ...In the United States IBM has a process for the collection of this battery For information call 1 800 426 4333 Have the IBM part number for the battery unit available when you call C004 C009 CAUTION o...

Page 14: ...2 CAUTION This product might be equipped with a hard wired power cable Ensure that a licensed electrician performs the installation per the national electrical code C022 xii Installation and User s Gu...

Page 15: ...d devices are not to be used as shelves or work spaces Do not place objects on top of rack mounted devices v Each rack cabinet might have more than one power cord Be sure to disconnect all power cords...

Page 16: ...d drawers This drawer is a fixed drawer and must not be moved for servicing unless specified by the manufacturer Attempting to move the drawer partially or completely out of the rack might cause the r...

Page 17: ...ipment and shall be easily accessible v Never install the system near liquids or in an excessively damp environment v Never let a foreign body penetrate inside the system v Never block the ventilation...

Page 18: ...xvi Installation and User s Guide...

Page 19: ...v License Agreement for Machine Code This document is provided on the IBM Documentation CD and it contains the translated license agreement for the product v Warranty Information This multilingual doc...

Page 20: ...lene terephthalat PET 01 High density polyethylene HDPE 02 Polyvinyl chloride PVC 03 Low density polyethylene LDPE 04 Polypropylene PP 05 Polystyrene PS 06 Follow all local regulations for the disposa...

Page 21: ...Management ABM technology that uses advanced battery management to increase battery service life optimize recharge time and provide a warning before the end of useful battery life v Selectable High E...

Page 22: ...4 Installation and User s Guide...

Page 23: ...Weights lb kg Dimensions inch mm D x W x H 5595 1AX 24 4 11 5 13 6 x 5 9 x 9 1 345 x 150 x 233 5595 2AX 35 3 16 2 17 5 x 5 9 x 9 1 445 x 150 x 233 5595 1KX 24 4 11 5 13 6 x 5 9 x 9 1 345 x 150 x 233...

Page 24: ...wer Off RPO control Outlets for connection of critical equipment Primary outlet group Outlet Group 1 programmable outlets for connection of equipment Outlet Group 2 programmable outlets for connection...

Page 25: ...critical equipment Primary outlet group Outlet Group 1 programmable outlets for connection of equipment Outlet Group 2 programmable outlets for connection of equipment Socket for connection to AC powe...

Page 26: ...ting and maintenance on page 29 for additional information LCD description After 5 minutes of inactivity the LCD displays the screen saver The LCD backlight automatically dims after 10 minutes of inac...

Page 27: ...g the equipment In AVR mode No beep The UPS is operating normally but the utility voltage is outside normal mode thresholds The UPS is powering the equipment through an Automatic Voltage Regulation de...

Page 28: ...on or Menu function Measurements Load W VA Load A pf Output V Hz Input V Hz Battery V min Efficiency Power usage Control Load Segments Outlet Group 1 ON OFF Outlet Group 2 ON OFF These commands overru...

Page 29: ...e list Menus status notices and alarms UPS fault Event Log data and settings are in all supported languages English User selectable when UPS is powered for the first time LCD settings Modify LCD scree...

Page 30: ...reduces lower input voltage to 70 V before UPS transfers to battery power This can be used if the load can withstand low voltage supply Normal mode Sensitivity High Low High for sensitive equipment UP...

Page 31: ...s 2 s 65354 s During a power outage authorizes UPS to turn off power to equipment connected to Outlet Group 1 and or Outlet Group 2 outlets This feature allows the shedding of non critical loads in o...

Page 32: ...d Disabled If mains recover during a shutdown sequence If Enabled shutdown sequence will complete and wait 10 seconds prior to restart if set to Disable shutdown sequence will not complete and restart...

Page 33: ...put Disabled Sleep mode Enabled Disabled If Disabled LCD and communication will turn OFF immediately after UPS is OFF If Enabled LCD and communication stays ON 1h30 min after UPS is OFF Disabled Remot...

Page 34: ...alarm triggers when the set percentage of battery capacity is reached during a back up time 20 Restart battery level 1 2 100 If set automatic restart will occur only when percentage of battery charge...

Page 35: ...ing materials must be disposed of in compliance with all local regulations concerning waste Recycling symbols are printed on the packing materials to facilitate sorting Battery module connection About...

Page 36: ...es Attach the front panel Installation of tower models Installing the communication card About this task Note It is not necessary to shut down the UPS before installing the UPS Network Management Card...

Page 37: ...1 1 Remove the connector panel blank which is secured by two screws 2 Insert the UPS Network Management Card into the slot 3 Secure the panel by tightening the two screws Chapter 3 Installation 19...

Page 38: ...20 Installation and User s Guide...

Page 39: ...rresponding signal Contact characteristics optocoupler v Voltage 48 V DC max v Current 25 mA max v Power 1 2 W Connecting the RS232 or USB communication port About this task Note The RS232 and USB com...

Page 40: ...UPS Network Management Card 1 1 Turn off the UPS 2 Disconnect the network cable 3 Remove the connector panel blank which is secured by two screws 4 Insert the UPS Network Management Card into the slo...

Page 41: ...normally and any loads are powered and protected The UPS should be in Normal mode Starting the UPS on battery power About this task Note Before using this feature the UPS must have been powered by uti...

Page 42: ...s solid v The audio alarm beeps every three seconds Note The remaining battery power is low Shut down all applications on the connected equipment because automatic UPS shutdown is imminent End of batt...

Page 43: ...e local ON OFF control using the button overrides the remote control function 4 Contact open UPS shutdown LED goes ON To return to normal operation deactivate the remote external contact and restart t...

Page 44: ...on features Power failure yes n a no yes Power sag yes n a no yes Power surge yes n a no yes Under voltage yes n a no yes Over voltage yes n a no yes Note High Efficiency mode introduces a delay betwe...

Page 45: ...ou prefer to power down to change the battery packs see Shutting down the UPS Note DO NOT DISCONNECT a battery pack while the UPS is in Battery mode Be aware the UPS can switch to Battery mode at any...

Page 46: ...remove the battery block and replace it Mounting the new battery pack Procedure Carry out the instructions in Removing the battery tray on tower models on page 27 in reverse order Note To ensure safet...

Page 47: ...properly If the condition persists contact your service representative Overload Power requirement exceeds the UPS capacity greater than 105 of nominal Remove some of the equipment from the UPS The UPS...

Page 48: ...pair is required you will be given a Returned Material Authorization RMA number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging...

Page 49: ...e Tier 2 customer replaceable unit You may install a Tier 2 CRU yourself or request IBM to install it at no additional charge under the type of warranty service that is designated for your product For...

Page 50: ...32 Installation and User s Guide...

Page 51: ...A 770W 8 4A 50 60Hz 1ph 100VAC 1080VA 825W 10 8A 120VAC 1440VA 1100W 12A 125VAC 1440VA 1100W 12A Output on battery power v Voltage v Frequency 100 120 V 10 6 1 50 60 Hz 0 1 Hz Battery sealed lead acid...

Page 52: ...r 200 V 1035 VA 693 W 1395 VA 990 W AC Input power 200 240VAC 50 60Hz 1ph 5 3A max 200 240VAC 50 60Hz 1ph 7 1A max AC Output power 50 60Hz 1ph 200VAC 1035VA 693W 5 2A 208VAC 1035VA 693W 5 2A 220VAC 11...

Page 53: ...240 V must be set to the identical AC power source value When the appliance is used in the EU use an external circuit breaker in front of line with rating 16 A 250 V which is IEC EN 60898 1 standard c...

Page 54: ...36 Installation and User s Guide...

Page 55: ...nce contract Your IBM service technician will request that you upgrade your software and firmware if the problem has a documented solution within a software upgrade v If you have installed new hardwar...

Page 56: ...available at http www ibm com supportportal How to send DSA data to IBM Use the IBM Enhanced Customer Data Repository to send diagnostic data to IBM Before you send diagnostic data to IBM read the te...

Page 57: ...00 IBM SERV 1 800 426 7378 In the U S and Canada hardware service and support is available 24 hours a day 7 days a week In the U K these services are available Monday through Friday from 9 a m to 6 p...

Page 58: ...40 Installation and User s Guide...

Page 59: ...BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF NON INFRINGEMENT MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE Some states do not allow disclaimer of express or implied warranties in certain trans...

Page 60: ...n intrinsic finite number of write cycles that the cell can incur Therefore a solid state device has a maximum number of write cycles that it can be subjected to expressed as total bytes written TBW A...

Page 61: ...enters a data center must be filtered to 99 97 efficiency or greater using high efficiency particulate air HEPA filters that meet MIL STD 282 v The deliquescent relative humidity of the particulate co...

Page 62: ...may not cause harmful interference and 2 this device must accept any interference received including interference that might cause undesired operation Industry Canada Class A emission compliance stat...

Page 63: ...hinweis versehen werden Warnung Dieses ist eine Einrichtung der Klasse A Diese Einrichtung kann im Wohnbereich Funk St rungen verursachen in diesem Fall kann vom Betreiber verlangt werden angemessene...

Page 64: ...Electronics and Information Technology Industries Association JEITA statement Japan Electronics and Information Technology Industries Association JEITA Confirmed Harmonics Guidelines products less tha...

Page 65: ...Taiwan Class A compliance statement Appendix C Notices 47...

Page 66: ...48 Installation and User s Guide...

Page 67: ...tery discharge beyond the permissible limit resulting in irreversible damage to the battery Load Devices or equipment connected to the UPS output Low battery warning A battery level indicating that ba...

Page 68: ...50 Installation and User s Guide...

Page 69: ......