LED behaviors for expansion enclosures are described in the table below.
Table 18. Expansion module LED states
CRU OK (green)
CRU Fault (amber)
SAS port activity
(green)
Status
On
Off
Expansion module OK
Off
On
Expansion module fault
section.
Off
No external port
connection
On
HD mini-SAS port
connection – no activity
Blinking
HD mini-SAS port
connection – activity
Blinking
IOM VPD error
Actions:
• If the Power OK LED is blinking, wait for the system to boot.
• If the Power OK LED is off, and the IOM is powered on, the module has failed.
– Check that the IOM is fully inserted and latched in place, and that the enclosure is powered on.
– Check for logs pertaining to the failure
• If the Fault LED is on, a fault condition is detected
– Re-seat the IOM in its slot.
– Check for logs pertaining to the failure
• If the above actions do not resolve the fault, contact IBM support for assistance.
Temperature sensors
Temperature sensors throughout the enclosure and its components monitor the thermal health of the
storage system. Exceeding the limits of critical values will cause a notification to occur.
Enclosure system
Overview
The following sections describe common problems that can occur with your enclosure system, and some
possible solutions. For the problems listed in the table below, the pertinent fault LEDs on the enclosure
front panel will light amber to indicate a fault. See also “Front panel LEDs” on page 14.
Table 19. Alarm conditions
Status
Severity
Alarm
PSU alert - loss of DC power from
a single PSU
Fault - loss of redundancy
S1
1
Chapter 6. Troubleshooting and problem solving 49