© Copyright IBM Corporation 2020, 2021. Customer Install Guide, Connector Node
17
Cloud Pak for Data System Connector
Node Hardware Specifications
Hardware specifications below provide information for the Cloud Pak for Data System
Connector Node, including dimensions, electrical power and cooling. .
All component installation documents are available on the Safety and Regulatory CD
that comes with your Cloud Pak for Data System components.
3453-F7E, Cloud Pak for Data System Connector Node [see Notes 1, 2]
Table 1
Width
Depth
Height
EIA
units
Weight
Amperage
(Max)
Power
(Max)
Cooling
(Max)
445 mm
(17.5 in)
764 mm
(30.1 in)
87 mm
(3.4 in)
2
20.4 kg
(45 lb)
4.1 amps
750
watts
2560
BTU/Hr
Notes:
[1] The power supplies automatically accept any voltage within the 200-240 V AC,
50/60 Hz rated-voltage range. If dual power supplies are installed and operating, the
power supplies draw approximately equal current from the utility (electrical supply) and
provide approximately equal current to the load.
[2] Power draw and heat load vary greatly by configuration and workload. When you
plan for an electrical system, it is important to use the maximum values but actual power
and cooling will be less.