7
Table 6. IBM 3000VA UPS (230V) runtime chart
Load
Run time on batteries
Percent Load
VA
Watts
Run time with standard internal
battery only
Run time with internal battery plus
External Battery Module (EBM)
25%
710
670
41 minutes
156 minutes
50%
1450
1350
17 minutes
81 minutes
75%
2160
2020
10 minutes
41 minutes
100%
2880
2680
7 minutes
27 minutes
Note: Battery backup times are approximate and may vary with equipment, configuration, battery age,
and temperature.
Physical specifications
Here are the physical specifications of the 3U uninterruptible power supply:
Height: 127 mm (5.0 in)
Width: 438 mm (17.2 in)
Depth: 527 mm (20.8 in)
Weight: 53953AX - 38.5 kg (84.8 lb) / 53953JX - 39.2 kg (86.4 lb) / 53953KX - 40.9 kg (90.1 lb)
Here are the physical specifications of the 3U Extended Battery Module:
Height: 127 mm (5.0 in)
Width: 438 mm (17.2 in)
Depth: 527 mm (20.8 in)
Weight: 119 lb
Operating environment
The IBM 3000VA LCD 3U Rack UPS is supported in the following environment:
Temperature:
Operation: 0 to 40 °C (32 to 104 °F)
Storage: -15° to 30° C (5° to 86° F) - charge the UPS battery every six months
Storage: 30° to 45° C (86° to 113° F) - charge the UPS battery every three months
Relative humidity: 5 to 95%
Maximum altitude:
Operation: 3,000 m (10,000 ft)
Storage: 15,000 m (50,000 ft)
Warranty
The IBM 3000VA LCD 3U Rack UPS has a three-year limited warranty.