Table 3. Specifications (Part 2 of 2)
Specification
IBM 3000VA LCD 3U Rack
UPS (100V/120V)
IBM 3000VA LCD 3U Rack
UPS (200V/208V)
IBM 3000VA LCD 3U
Rack UPS (230V)
Communications and management
USB port
Yes
Yes
RS-232 serial port
Yes
Yes
Ethernet port
Optional using Network Management Card, 46M4110
Environmental Monitoring
Probe
Optional Environmental Monitoring Probe, 46M4113
Surge Protection and Filtering
Surge energy rating
1200 Joules
2400 Joules
2400 Joules
Filtering
ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
Battery run times and recharge times
The following tables list the expected period that the UPS will operate solely on batteries. Table 4 is for
the 100V/120V model, Table 5 is for the 200/208V model, and Table 6 is for the 230V model.
Table 4. IBM 3000VA UPS (100V/120V) runtime chart
Load
Run time on batteries
Percent
Load
VA
Watts
Run time with standard internal
battery only
Run time with internal battery plus
External Battery Module (EBM)
25%
720
678
42 minutes
156 minutes
50%
1440
1350
16 minutes
62 minutes
75%
2160
2060
10 minutes
42 minutes
100%
2880
2700
7 minutes
27 minutes
Table 5. IBM 3000VA UPS (200V/208V) runtime chart
Load
Run time on batteries
Percent Load VA
Watts
Run time with standard internal
battery only
Run time with internal battery plus
External Battery Module (EBM)
25%
710
660
41 minutes
153 minutes
50%
1420
1340
17 minutes
68 minutes
75%
2140
2040
10 minutes
43 minutes
100%
2810
2660
6 minutes
29 minutes