background image

• 

The MicroMax750 is part of a range of control units adapted, with the necessary 

additional functions, for optimum control of rotary heat exchangers.  

The series consists of five sizes, MicroMax, MicroMax180, MicroMax370,  

MicroMax750 and MicroMax1500.  

All of the control units drive three-phase asynchronous motors with associated 

gearing, the control unit designation denotes motor output. All control units 

have an input signal of 0-10 V.

• 

MicroMax750 is designed for rotors up to 5000 mm with a rotor speed of  

max 12 rpm.  

If a faster rotor speed is necessary, rotor diameter should be reduced.

• 

Heat exchanger rpm and thus thermal efficiency are governed by the control unit 

so that rotor speed is proportional to the input signal from the control centre.

• 

MicroMax750 a adjustable threshold value of 0-2 V. 

• 

MicroMax750 has adjustable boost function.

• 

MicroMax750 has a rotation monitor (magnet mounted on the rotor with 

associated magnetic sensor) and built-in cleaning function. 

The functions can be disconnected via DIP switches.

• 

MicroMax750 starts automatically following voltage  

drop-out and resets all alarms on restart.

• 

The motor should not be disconnected from the control unit while under load.

DESCRIPTION OF FUNCTIONS

5

Summary of Contents for MicroMax750

Page 1: ...L UNIT FOR ROTARY HEAT EXCHANGER MicroMax750 Article no F21075301 Set of EMC glands as an option With adjustable boost function and threshold value M ade in S w ed en Since 1983 Since 1983 Ska vara 25...

Page 2: ......

Page 3: ...on of functions 5 Technical data 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Reset 9 Connection diagram 10 Connections 10 Checks before powering up the...

Page 4: ...sal and recycling When replacing components or when the control unit in its entirety need replacing please follow the advice below The aim should always be maximum possible recycling of raw materials...

Page 5: ...ower before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electric shock resulting in serious injury or death Connected terminals contain r...

Page 6: ...magnetic Compatibility Regulations 2016 The Electrical Equipment Safety Regulations 2016 The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2...

Page 7: ...12 rpm If a faster rotor speed is necessary rotor diameter should be reduced Heat exchanger rpm and thus thermal efficiency are governed by the control unit so that rotor speed is proportional to the...

Page 8: ...fuse max 10 A Output voltage 3x0 230 V Output frequency 5 100 Hz Min frequency Fixed 5 Hz Max frequency 40 100 Hz Motor output max 750 W Motor current 3 6 A Overload 2 min 30 min 5 3 A Internal fuse...

Page 9: ...DIP switch is set to OFF Low speed The rotor rotates at the fixed minimum rpm when the switch is set to ON After a test run make sure the DIP switch is set to OFF Manual operation test mode OPERATIONA...

Page 10: ...the motor reverts to normal mode when the temperature drops See Overcurrent on page 9 Overvoltage Alarms and trips if the connection voltage exceeds 276 V for more than 4 5 seconds Undervoltage Alarms...

Page 11: ...R Boost Torque boost at low rpm May be increased if necessary but motor temperature will increase Factory setting at 9 o clock Threshold value The control unit will start when the input signal exceeds...

Page 12: ...overheating Must be jumped if the temperature switch is not connected Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max 2 A resistive load 250 V AC Manual spee...

Page 13: ...rpm Set the High Speed DIP switch to the ON position Adjust Max rpm so that the rotor rotates at 10 12 rpm or as per directions from rotor manufacturer After a test run set the DIP switch to OFF Check...

Page 14: ...GLAND Motor lflex Classic 110 CY 7G0 75 Shielded Connection voltage 3G1 5 Not shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Di...

Page 15: ...PERSONAL NOTES 13...

Page 16: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 42 33 00 10 www ibccontrol se info ibccontrol se IBCcontrol F21075902GB Version 1 0 1 2021 10 01...