background image

4

MANUFACTURER´S DECLARATION
DECLARATION OF CONFORMITY

Manufacturer

IBC control AB

Brännerigatan 5 A

SE-263 37 Höganäs

Sweden

Tel: +46 42 33 00 10

Product

Control unit for rotary heat exchanger

Type designation

MicroMax750

Applicable  

EU Directives

EMC Directive 2014/30/EU

Low Voltage Directive 2014/35/EU

RoHS Directive 2011/65/EU including Delegated Directive EU2015/863

Applicable  

UK Directives

The Electromagnetic Compatibility Regulations 2016 

The Electrical Equipment (Safety) Regulations 2016 

The Restriction of the Use of Certain Hazardous Substances in Electrical and 

Electronic Equipment Regulations 2012

Harmonizing  

standards for  

EU/UK Directives

BS EN 61800-3:2004/A1:2012 - Emission kategori C1, Immunitet second 

environment 

BS EN 61800-5-1:2007/A1:2017 - The control unit is intended for installation 

in environments with a pollution rating of 2 (Pollution degree 2)

This declaration of conformity is issued under the full responsibility of the 

manufacturer

   

 

      

  
  

                                                                    

Höganäs 2021-09-01

  

 

  

                                                    

IBC control AB

 

 

   

 

 

   

 

 

     

    

   Christer Persson

     

 

  

                                                    

MD

Summary of Contents for MicroMax750

Page 1: ...L UNIT FOR ROTARY HEAT EXCHANGER MicroMax750 Article no F21075301 Set of EMC glands as an option With adjustable boost function and threshold value M ade in S w ed en Since 1983 Since 1983 Ska vara 25...

Page 2: ......

Page 3: ...on of functions 5 Technical data 6 Functions 6 DIP switch 7 Operational indications 7 Alarms 8 9 Settings via potentiometer 9 Reset 9 Connection diagram 10 Connections 10 Checks before powering up the...

Page 4: ...sal and recycling When replacing components or when the control unit in its entirety need replacing please follow the advice below The aim should always be maximum possible recycling of raw materials...

Page 5: ...ower before removing the cover Never touch electrical components or contacts while main current is switched on Risk of electric shock resulting in serious injury or death Connected terminals contain r...

Page 6: ...magnetic Compatibility Regulations 2016 The Electrical Equipment Safety Regulations 2016 The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment Regulations 2...

Page 7: ...12 rpm If a faster rotor speed is necessary rotor diameter should be reduced Heat exchanger rpm and thus thermal efficiency are governed by the control unit so that rotor speed is proportional to the...

Page 8: ...fuse max 10 A Output voltage 3x0 230 V Output frequency 5 100 Hz Min frequency Fixed 5 Hz Max frequency 40 100 Hz Motor output max 750 W Motor current 3 6 A Overload 2 min 30 min 5 3 A Internal fuse...

Page 9: ...DIP switch is set to OFF Low speed The rotor rotates at the fixed minimum rpm when the switch is set to ON After a test run make sure the DIP switch is set to OFF Manual operation test mode OPERATIONA...

Page 10: ...the motor reverts to normal mode when the temperature drops See Overcurrent on page 9 Overvoltage Alarms and trips if the connection voltage exceeds 276 V for more than 4 5 seconds Undervoltage Alarms...

Page 11: ...R Boost Torque boost at low rpm May be increased if necessary but motor temperature will increase Factory setting at 9 o clock Threshold value The control unit will start when the input signal exceeds...

Page 12: ...overheating Must be jumped if the temperature switch is not connected Alarm relay 13 14 15 Closes between 14 15 in the event of an alarm or voltage drop out Max 2 A resistive load 250 V AC Manual spee...

Page 13: ...rpm Set the High Speed DIP switch to the ON position Adjust Max rpm so that the rotor rotates at 10 12 rpm or as per directions from rotor manufacturer After a test run set the DIP switch to OFF Check...

Page 14: ...GLAND Motor lflex Classic 110 CY 7G0 75 Shielded Connection voltage 3G1 5 Not shielded EMC glands must be used for shielded cables The above cables or equivalent must be used to comply with the EMC Di...

Page 15: ...PERSONAL NOTES 13...

Page 16: ...IBC control AB Br nnerigatan 5 A SE 263 37 H gan s Sweden Tel 46 42 33 00 10 www ibccontrol se info ibccontrol se IBCcontrol F21075902GB Version 1 0 1 2021 10 01...

Reviews: