Symptom
Diagnosis
Solution
Boiler
Maximum
Supply Temp.
setting too low
Make sure the Maximum Supply Temp. setting is at least 10°F higher than the
DHW Supply Setpoint PLUS 1/2 of the Supply Diff’l Temp setting.
Water at
faucets
too hot
DHW
temperature
setting too
high
Reduce the DHW Tank Set Point temperature
DHW
temperature
sensor giving
false reading
Sensor is not fully inserted into the well
Sensor giving incorrect resistance reading
Sensor connected to IBC Therm terminals instead of DHW Sensor
terminals
Improper 3rd party sensor installed in well