
IWT 119 Max (135 °F)
Boiler
Output
(BTU/Hr)
Boiler Flow = 25 gpm / 160 °F
Boiler Flow - 25 gpm / 180°F
1st Hour Rating
(Gal/Hr)
Continuous rating
(Gal/Hr) 58°F entering
cold water
1st Hour Rating
(Gal/Hr)
Continuous rating
(Gal/Hr) 58°F entering
cold water
200,000
357
249
418
311
220,000
381
274
448
342
240,000
405
299
479
373
250,000
418
311
494
389
300,000
479
373
570
467
350,000
539
435
646
544
380,000
576
473
692
591
400,000
600
498
722
622
420,000
625
523
753
653
Table 9
Recovery rates - IWT 119-Max
Pressure drop vs boiler flow
Pressure Drop (ft of water) vs Boiler Flow
Model
10 gpm
14 gpm
25 gpm
IWT 40
3.3
6.2
-
IWT 50
4.0
7.0
-
IWT 65
4.4
7.5
-
IWT 80
5.4
10.1
-
IWT 119
6.5
11.8
-
IWT 80 Max
8.0
14.4
16.7
IWT 119 Max
8.0
14.4
16.7
Table 10
Pressure drop vs boiler flow - all models
13
Section: Specifications
Summary of Contents for IWT 119
Page 2: ......