
6.7.6 Buffer tank sizing
At the planning stage it is important to consider whether a buffer tank will be needed to
prevent short-cycling. Repeated short-cycling can lead to premature compressor failure and
other component damage. Good practice is to design for a minimum cycle time of ten
minutes. To calculate the buffer tank size required:
where:
V= minimum volume of buffer tank (US gallons)
t = desired minimum cycle time (minutes); IBC recommends 10
Q = heat source output rate, i.e. minimum output (Btu/h)
q = lowest rate of heat extraction from tank: may be zero (Btu/h)
ΔT = tank differential (°F); IBC recommends 10 and advises this should not exceed
20°F
Quick calculation for buffer tank sizing
6.7.7 Quick calculation for buffer tank sizing
The buffer tank volume in gallons can be quickly calculated by taking the minimum output in
MBtu/h and multiplying by two. (This presumes the tank temperature can vary by 10°F.)
where:
V= minimum volume of buffer tank (US gallons)
Q = minimum heat source output rate (Btu/h)
Example: if the Heat Pump's minimum output is 20MBH (read from the lowest modulation (30
Hz) chart), 20 X 2 = 40; thus the buffer tank's minimum size is 40 gallons.
34
Section: Installation
Summary of Contents for HPX 3
Page 10: ...3 3 Capacities and COPs 10 Section Specifications...
Page 11: ...Table 2 HPX 3 Capacity and COP tables 11 3 3 Capacities and COPs...
Page 12: ...12 Section Specifications...
Page 13: ...Table 3 HPX 5 Capacity and COP tables 13 3 3 Capacities and COPs...
Page 14: ...Intentionally left empty...
Page 20: ...Intentionally left empty...
Page 48: ...Intentionally left empty...
Page 50: ...Intentionally left empty...
Page 64: ...Intentionally left empty...
Page 65: ...65 13 0 Appendices Wiring diagrams Figure 19 HPX 3 internal wiring diagram...
Page 66: ...Figure 20 HPX 5 internal wiring diagram 66 Section Appendices...