6.7.5 Buffer tank piping
Hydronic Heat Pump circulator with integral check valve
Glycol fill tank: 25%-50% propylene glycol throughout system. Alternatively, a flat plate
heat exchanger or heat pump indirect tank can isolate glycol from distribution water (see
previous figures).
Buffer tank.
Buffer tank hydraulically separates HPX from load piping; load pump(s) sized for head
loss of building side of tank only. Buffer tank needs vacuum breaker for cooling mode.
Figure 12
Hydronic Heat Pump with buffer tank
33
6.7.5 Buffer tank piping