
6.7.4 Glycol isolation with indirect / buffer tank
Hydronic Heat Pump circulator with integral check valve
Glycol fill tank.
Extended-coil buffer tank for glycol isolation. Note extra surface area of specialty heat
pump indirect tank for efficient heat transfer: domestic model of indirect tank would
likely cause short-cycling. Buffer tank needs vacuum breaker for cooling mode.
Fill valve and expansion tank to maintain system pressure
Figure 11
Glycol isolation using extended coil indirect buffer tank
32
Section: Installation
Summary of Contents for HPX 3
Page 10: ...3 3 Capacities and COPs 10 Section Specifications...
Page 11: ...Table 2 HPX 3 Capacity and COP tables 11 3 3 Capacities and COPs...
Page 12: ...12 Section Specifications...
Page 13: ...Table 3 HPX 5 Capacity and COP tables 13 3 3 Capacities and COPs...
Page 14: ...Intentionally left empty...
Page 20: ...Intentionally left empty...
Page 48: ...Intentionally left empty...
Page 50: ...Intentionally left empty...
Page 64: ...Intentionally left empty...
Page 65: ...65 13 0 Appendices Wiring diagrams Figure 19 HPX 3 internal wiring diagram...
Page 66: ...Figure 20 HPX 5 internal wiring diagram 66 Section Appendices...