INSTALLATION AND OPERATION INSTRUCTIONS
2-4
DC SERIES COMBI BOILERS
DC 23-84, DC 29-106, DC 33-124, DC 33-160
2.3.4 Table of Programmable Parameters
PARA-METER DESCRIPTION
DEFAULT
RANGE / OPTIONS
USER SET UP
Boiler Supply Temperature
180°F (82°C)
86°F (30°C) to 194°F (90°C)
Tankless Domestic Hot Water
Temperature
120°F (49°C)
104°F (40°C) to 149°F (65°C)
15 - INSTALLER SET UP MENU
1
System Type
(SEE CHART BELOW FOR
ADDITIONAL DETAILS)
DC series = 0
HC series = 3
DC - 0 – Both Space Heating and Tankless DHW
HC - 1 – Space Heating and Indirect DHW Tank
DC - 2 – Tankless DHW Only
HC - 3 – Space Heating Only
DC - 4 – Space Heating and Tankless DHW with
a Storage Tank
DC - 5 – Tankless DHW with a Storage Tank Only
DC – 6 – Space Heating, Indirect DHW Tank and
Tankless DHW
3
Maximum Power available for
Space Heating
100%
Parameter “c” value to 100%
5
Min Heating Curve Supply Water
Temp
90F (32°C)
50°F (20°C) to 194°F (90°C)
Must be at least 18°F (10°C) lower than
Parameter “5.”
5.
Max Heating Supply Water Temp
194°F (90°C)
Range 86°F (30°C) to 194°F (90°C)
6
Min Outdoor Design Temp
14°F (-10°C)
Range to -22°F (-30°C) to 55°F (13°C)
7
Summer Shut Down Temperature
64°F (18°C)
Range 59°F (15°C) to 86°F(30°C)
Pump will run but the burner will not fire if
Outdoor Temperature is above this setting
8
Internal Boiler Pump Post Purge
1 min
Range 0 min to 15 min
9
External DHW Pump Post Purge
1 min
Range 0 min to 15 min
C
Burner Modulation (Ramp up)
with a Space Heating Demand
1
0 = OFF
1 = ON
2 = Open Therm control
E
Minimum Space Heating
Temperature with an Open Therm
heating demand
104°F (40°C)
50°F – 140°F (10°C – 60°C)
Only for use with an Open Therm thermostat
E.
Open Therm or RF Space Heating
Control
1
0 = Ignore a call for heat if the target temperature
is less than “E”
1 = Answer a call for heat with a temperature
equal to “E”
2 = Answer a call for heat with a temperature
equal to that set in the user menu “Boiler
Maximum Temperature”
F
Fan RPM at Burner Start for
Space Heating
Model Dependent
50-100% of High Fire
DC 23-84 = 70
DC 29-106 = 60
DC 33-124 = 50
DC 33-160 = 40 (Range = 40-75)
NOTE:
The control displays codes that include upper and lower case letter and a combination with a period after the letter.
Example: C, c., c are all valid parameter codes. When adjusting settings, double check that you are in the correct parameter.