INSTALLATION AND OPERATION INSTRUCTIONS
2-6
DC SERIES COMBI BOILERS
DC 23-84, DC 29-106, DC 33-124, DC 33-160
PARAMETER 1
SETTINGS
LOAD PRIORITY:
0 = HIGHEST
PARAMETER NUMBER 1: DETAILED DESCRIPTION
0
0 = Tankless DHW
1 = Space Heating
DC Models – Both Space Heating and Tankless DHW
•
Internal Boiler Pump is enabled with a call for Space Heating
•
Internal Boiler Pump is disabled with a call for Tankless DHW
1
0 = Indirect DHW Tank Sensor
or Aquastat
1 = Space Heating
HC Models – Space Heating and Indirect DHW Tank
•
Aquastat or Sensor connected to X4.9 and X4.10
•
Internal Boiler Pump is enabled for both Space Heating and for DHW
heating
•
External Pump Terminals 4,5,6 (120Vac - 1Amp Max) enabled with a
call for DHW
2
0 = Tankless DHW
DC Models – Tankless DHW Only
•
DHW only, Space Heating Disabled
•
Internal Pump disabled
3
0 = Space Heating
HC Models – Space Heating Only
•
Internal Boiler Pump is enabled with a call for Space Heating
4
0 = DHW Storage Tank Sensor
or Aquastat
1 = Space Heating
DC Models – Space Heating and Tankless DHW with a Storage Tank
•
Aquastat or Sensor connected to X4.9 and X4.10
•
External Pump Terminals 4,5,6 (120Vac - 1Amp Max) enabled with a
call for DHW
•
Internal Boiler Pump is enabled with a call for Space Heating
•
Internal Boiler Pump is disabled with a call for Tankless DHW
•
External DHW Pump is enabled with a call for Tankless DHW
5
0 = DHW Storage Tank Sensor
or Aquastat
DC Models – Tankless DHW with a Storage Tank Only
•
Space Heating is disabled
•
Aquastat or Sensor connected to X4.9 and X4.10
•
External Pump Terminals 4,5,6 (120Vac - 1Amp Max) enabled with a
call for DHW
•
Internal Boiler Pump disabled
•
Internal Boiler Pump is disabled with a call for Tankless DHW
6
0 = Tankless DHW
1 = Indirect DHW Tank Sensor
or Aquastat
2 = Space Heating
DC Models – Space Heating, Indirect DHW Tank and Tankless DHW
•
External Pump Terminals 4,5,6 (120Vac - 1Amp Max) enabled with a
call for DHW
•
Internal Boiler Pump is enabled for both Space Heating and for Indirect
DHW
•
Internal Boiler Pump is disabled with a call for Tankless DHW
NOTE:
The control displays codes that include upper and lower case letter and a combination with a period after the letter.
Example: C, c., c are all valid parameter codes. When adjusting settings, double check that you are in the correct parameter.
Summary of Contents for DC 23-84