BT INDIRECT SERIES – WATER HEATERS

NOTE

When using zone valves in a 

multi-zone heating system, 

careful consideration must 

be taken to ensure that flow 

rates do not decrease below 

the boiler’s rated minimum 

flow requirement. Bypass 

arrangements (pressure 

activated bypass, three way 

valves, etc.) may be required 

to ensure adequate flow 

under low load conditions.

BT Series Indirect 

Hot Water Tank

120VAC

(HOT)     (COM)

Heating circ.

AC in

Primary 

Pump

Boiler 

Pump

yellow

L
N

L
N

white

white

black

DHW circ.

Factory-installed  

Ganged endswitches from 

Heating zone valves

Aquastat -dry contact

G

Fie

ld

-w

irin

Bundl

e

Select one: 

either 

a dry-contact 

Aquastat to a 

Therm

. connection 

or 

a 10K Ohm thermister to the 

DHW Sensor

 connection.

Figure 4: Piping Suggestion for IBC SL Series Small Boilers with Side Connections

Figure 5: Wiring Suggestion for IBC Boilers

Summary of Contents for BTI 119-MAX

Page 1: ...is completed keep this manual with the water heater Product complies with NSF ANSI 372 and conforms with lead content requirement for lead free plumbing as defined by the California Vermont Maryland a...

Page 2: ...if it has been damaged or dropped 5 Installation start up and servicing of IBC Indirect Water Heaters must be done with due care and attention and should only be performed by competent qualified licen...

Page 3: ...r 7 2 6 Temperature and Pressure Relief Valve 8 2 7 Additional Recommended Components 8 2 8 Removing the Existing Domestic Water Heating System 8 2 9 Water Quality 9 3 0 PIPING 10 3 1 Domestic Water P...

Page 4: ...event scalding injuries Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the water heater This water heater contains components that become very hot when...

Page 5: ...0 BTI 80 MAX 79 9 70 0 23 8 1 1 1 2 3 4 1 141 1 BTI 119 MAX 114 6 65 75 28 9 1 1 2 1 1 2 3 4 1 177 5 Table 1 Dimensions and Capacities Maximum Allowable Working Pressure 150 psi Hydrostatically teste...

Page 6: ...capacity the water heating output will be reduced 3 Circulator sizing Refer to Table 2 for the flow through the water heater coil and the pressure drop at minimum flow Calculate the pressure drop acr...

Page 7: ...in an area where water leakage from the tank or connections will not result in damage to areas adjacent to the water heater or to lower floors of the structure When such a location can not be avoided...

Page 8: ...nkless Heaters Disconnect the domestic piping Do not plug the cold water or the hot water fittings in the internal tankless coil Leave the coil in the boiler with the cold and hot water fittings open...

Page 9: ...ater Quality Improper water quality will reduce the expected life of the water heater Hard water sediment high or low pH and high levels of chlorides in the domestic water should be avoided Sediment a...

Page 10: ...ns in the faucets Check the system for leaks Repair as required 3 2 Boiler Water Piping See Figures in Section 8 0 1 Determine where the boiler the space heating and the water heater connections shoul...

Page 11: ...ter connection labeled BOILER SUPPLY should be piped to the boiler supply piping after the air purger and grouped with the other zone supplies The use of a shut off valve is recommended for future ser...

Page 12: ...he temperature of the sensed environment and compare with the value derived from the measurement of the resistance obtained by connecting a good quality test meter capable of measuring up to 5 000 k 5...

Page 13: ...ube sensing bulb so that it is at a right angle to the back of the control Loosen the mounting screw and carefully insert the sensing bulb into the well until the control mounts to the well head Tight...

Page 14: ...will have to be used and the thermostat must go through the cycle of heating cold water and satisfying at the new lower temperature Additional temperature checks should follow the completion of a heat...

Page 15: ...m chemical cleaning may be required Proceed as follows 6 1 Chemical Cleaning of the Heating Coil 1 To avoid water damage shut off the cold water supply to the water heater 2 Make a note of the DHW tem...

Page 16: ...ue Water Heater Circulator does not operate Follow steps for Boiler does not operate Ensure the pump relay is closed and suppling power to the pump Ensure the zone valve is open and the end switch is...

Page 17: ...r and its fan on a call for heat This may result in operation of these components when other loads are running at a higher priority resulting in cold air blowing or robbing heat from another load Some...

Page 18: ...equired to ensure adequate flow under low load conditions BT Series Indirect Hot Water Tank 120VAC HOT COM Heating circ AC in Primary Pump Boiler Pump yellow L N L N white white black DHW circ Factory...

Page 19: ...19 INSTALLATION AND OPERATION INSTRUCTIONS BT INDIRECT SERIES WATER HEATERS Figure 6 Suggested Domestic Water Piping...

Page 20: ...INSTALLATION AND OPERATION INSTRUCTIONS 20 BT INDIRECT SERIES WATER HEATERS SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...

Page 21: ...21 INSTALLATION AND OPERATION INSTRUCTIONS BT INDIRECT SERIES WATER HEATERS NOTES...

Page 22: ...INSTALLATION AND OPERATION INSTRUCTIONS 22 BT INDIRECT SERIES WATER HEATERS NOTES...

Page 23: ...R1 JULY 2015 Initial release R2 SEPTEMBER 2015 Certified release R3 JUNE 2016 Updates to dimensions and capacities table updates to ratings table R4 JUNE 2017 Updates to drawings for side connections...

Page 24: ...IBC Technologies Inc 8015 North Fraser Way Burnaby BC Canada V5J 5M8 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 221A1 R4 June 2017 IBC Technologies Inc 2017...

Reviews: