INSTALLATION AND OPERATION INSTRUCTIONS

BT INDIRECT SERIES – WATER HEATERS

for primary/secondary systems, see primary loop space heating piping on 

Figure 

4: Piping Suggestion for IBC SL Series Small Boilers with Side Connections.

For parallel piping, see

 Figure 2: Generic Boiler Piping Schematic – Zoned by 

Circulator.

 Mount the water heater circulator as close as is practicable to the 

water heater, and make sure the flow arrow points toward the water heater. The 

use of shut-off valves is recommended for future service convenience.
The water heater connection labeled “BOILER RETURN” should be piped to the 

boiler return piping as close to the boiler as possible and after any flow control or 

check valves in the space heating return piping. The use of a union and a shut-off 

valve is recommended. The use of a check valve is required to prevent back flow 

through the water heater during operation of the space heating system.

3.4 Zone Valve System 

It is recommended that minimum size 1” pipe and 1” full-port zone valves with a 

high CV be used on the water heater zone to ensure adequate flow. 
The water heater connection labeled “BOILER SUPPLY” should be piped to the 

boiler supply piping after the air purger and grouped with the other zone supplies. 

The use of a shut-off valve is recommended for future service convenience.
The water heater connection labeled “BOILER RETURN” should be piped to the 

boiler return piping and grouped with the other zone returns. The use of a union 

and a shut-off valve is recommended. The use of a check valve is required to 

prevent back flow through the water heater during operation of the space heating 

system.

NOTE

The piping drawings in 

Section 8.0 of this manual 

are simple schematic guides 

to a successful installation. 

There are many necessary 

components not shown, 

and details such as thermal 

traps are left out so the 

drawings have greater clarity. 

We require that our boilers 

and tanks be installed by 

licensed and experienced 

trades people who are familiar 

with the applicable local 

and national codes. System 

design is to be completed 

by an experienced hydronic 

designer or Engineer.
The application drawing(s) 

shown in this manual are only 

part of the finished design.
It is absolutely neccessary 

to carefully read and follow 

these installation instructions, 

and just as importantly, the 

installation instructions or the 

boiler model you are using 

with this water heater.

Summary of Contents for BTI 119-MAX

Page 1: ...is completed keep this manual with the water heater Product complies with NSF ANSI 372 and conforms with lead content requirement for lead free plumbing as defined by the California Vermont Maryland a...

Page 2: ...if it has been damaged or dropped 5 Installation start up and servicing of IBC Indirect Water Heaters must be done with due care and attention and should only be performed by competent qualified licen...

Page 3: ...r 7 2 6 Temperature and Pressure Relief Valve 8 2 7 Additional Recommended Components 8 2 8 Removing the Existing Domestic Water Heating System 8 2 9 Water Quality 9 3 0 PIPING 10 3 1 Domestic Water P...

Page 4: ...event scalding injuries Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the water heater This water heater contains components that become very hot when...

Page 5: ...0 BTI 80 MAX 79 9 70 0 23 8 1 1 1 2 3 4 1 141 1 BTI 119 MAX 114 6 65 75 28 9 1 1 2 1 1 2 3 4 1 177 5 Table 1 Dimensions and Capacities Maximum Allowable Working Pressure 150 psi Hydrostatically teste...

Page 6: ...capacity the water heating output will be reduced 3 Circulator sizing Refer to Table 2 for the flow through the water heater coil and the pressure drop at minimum flow Calculate the pressure drop acr...

Page 7: ...in an area where water leakage from the tank or connections will not result in damage to areas adjacent to the water heater or to lower floors of the structure When such a location can not be avoided...

Page 8: ...nkless Heaters Disconnect the domestic piping Do not plug the cold water or the hot water fittings in the internal tankless coil Leave the coil in the boiler with the cold and hot water fittings open...

Page 9: ...ater Quality Improper water quality will reduce the expected life of the water heater Hard water sediment high or low pH and high levels of chlorides in the domestic water should be avoided Sediment a...

Page 10: ...ns in the faucets Check the system for leaks Repair as required 3 2 Boiler Water Piping See Figures in Section 8 0 1 Determine where the boiler the space heating and the water heater connections shoul...

Page 11: ...ter connection labeled BOILER SUPPLY should be piped to the boiler supply piping after the air purger and grouped with the other zone supplies The use of a shut off valve is recommended for future ser...

Page 12: ...he temperature of the sensed environment and compare with the value derived from the measurement of the resistance obtained by connecting a good quality test meter capable of measuring up to 5 000 k 5...

Page 13: ...ube sensing bulb so that it is at a right angle to the back of the control Loosen the mounting screw and carefully insert the sensing bulb into the well until the control mounts to the well head Tight...

Page 14: ...will have to be used and the thermostat must go through the cycle of heating cold water and satisfying at the new lower temperature Additional temperature checks should follow the completion of a heat...

Page 15: ...m chemical cleaning may be required Proceed as follows 6 1 Chemical Cleaning of the Heating Coil 1 To avoid water damage shut off the cold water supply to the water heater 2 Make a note of the DHW tem...

Page 16: ...ue Water Heater Circulator does not operate Follow steps for Boiler does not operate Ensure the pump relay is closed and suppling power to the pump Ensure the zone valve is open and the end switch is...

Page 17: ...r and its fan on a call for heat This may result in operation of these components when other loads are running at a higher priority resulting in cold air blowing or robbing heat from another load Some...

Page 18: ...equired to ensure adequate flow under low load conditions BT Series Indirect Hot Water Tank 120VAC HOT COM Heating circ AC in Primary Pump Boiler Pump yellow L N L N white white black DHW circ Factory...

Page 19: ...19 INSTALLATION AND OPERATION INSTRUCTIONS BT INDIRECT SERIES WATER HEATERS Figure 6 Suggested Domestic Water Piping...

Page 20: ...INSTALLATION AND OPERATION INSTRUCTIONS 20 BT INDIRECT SERIES WATER HEATERS SERVICE RECORD DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE...

Page 21: ...21 INSTALLATION AND OPERATION INSTRUCTIONS BT INDIRECT SERIES WATER HEATERS NOTES...

Page 22: ...INSTALLATION AND OPERATION INSTRUCTIONS 22 BT INDIRECT SERIES WATER HEATERS NOTES...

Page 23: ...R1 JULY 2015 Initial release R2 SEPTEMBER 2015 Certified release R3 JUNE 2016 Updates to dimensions and capacities table updates to ratings table R4 JUNE 2017 Updates to drawings for side connections...

Page 24: ...IBC Technologies Inc 8015 North Fraser Way Burnaby BC Canada V5J 5M8 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 221A1 R4 June 2017 IBC Technologies Inc 2017...

Reviews: