Manual ibaPADU-8-O

 
 

20 

Issue 1.9 

 

 

10 

Working with ibaPADU-8-O and ibaLogic V4 

10.1 

Hardware 

The ibaPADU-8-O must be connected to an ibaFOB-card with output capability, i. e. 
ibaFOB-io-D or ibaFOB-4i-/4o-D.  

The ibaFOB transmits the ibaLogic output image with an update rate of 1 ms to the out-
put devices. 

It is allowed to split a 3.3 Mbit/s fiber optic wire into multiple wires with the  
ibaBM-FOX-i-3o device. 

10.2 

Software Application 

The sending of output signals from ibaLogic to ibaPADU-8-O is done by connecting 
ibaFOB IO/OUT output resource channels. 

The device address of the ibaPADU-8-O and the ibaFOB IO/OUT output channel num-
ber are always closely related.  

Each of the 3.3 Mbit/s output links of an ibaFOB card transmits up to 64 analog and 64 
digital signals. A daisy-chain consisting of up to 8 ibaPADU-8-O devices can be con-
nected to each link. The mapping of signals is determined by the device address 1...8. 

 

 

Daisy-chain 

Analog signals 

0…7 

8…15 

16…23 

24…31 

32…39 

40…47 

48…55 

56…63 

Digital signals 

0…7 

8…15 

16…23 

24…31 

32…39 

40…47 

48…55 

56…63 

Device address 

 

Table 2: Mapping of signals and device address in ibaLogic V4 

 

Sample application with ibaLogic V4 

In order to create the same sample application like with ibaLogic V3 before, follow 
these steps: 

1. 

Open the I/O configurator in ibaLogic-V4. The cards and input/output resources 
are listed in the tree on the left side. 

 

Summary of Contents for ibaPADU-8-O

Page 1: ...ibaPADU 8 O Parallel Analog Digital Converter for Analog and Digital Outputs Manual Issue 1 9...

Page 2: ...pliance is not guaranteed However the information in this publication is updated regularly Required corrections are contained in the following regulations or can be downloaded on the Internet The curr...

Page 3: ...2 Fiber optic connectors TX X10 and RX X11 11 6 5 3 Adjusting the device address with switch S1 11 6 5 4 Adjusting the device mode with switch S2 11 6 5 5 Connector pin outs X14 X1 X2 X5 X6 12 6 5 6...

Page 4: ...0 Working with ibaPADU 8 O and ibaLogic V4 20 10 1 Hardware 20 10 2 Software Application 20 11 Technical data 23 11 1 Main data 23 11 2 Analog outputs 23 11 3 Digital outputs 24 11 4 Dimensional drawi...

Page 5: ...sional if he she is capable of assessing safety and recognizing possible consequences and risks on the basis of his her special training knowledge and experience and knowledge of the standard regulati...

Page 6: ...s and the system or machine to be controlled there is a risk of death or severe injury The non observance of this safety information may result in a potential risk of death or severe injury The non ob...

Page 7: ...with the ibaLink SM 128V i 2o card the device may additionally be used as IO extension for standard VME systems such as Converteam ALSTOM AEG C80 A800 Logidyn D1 Converteam ALSTOM AEG ALSPA C80 HPC Lo...

Page 8: ...l clip at the back of the device fits properly into the top edge of the DIN rail and then lightly press the device down back into the DIN rail The device will easily snap into the DIN rail After that...

Page 9: ...igital output 0 can be used as pulse generator in mode 2 6 2 PC side connection with ibaFOB cards In order to connect a PC with the device an ibaFOB D output card should be used The card is activated...

Page 10: ...Fiber optic output X10 Address switch S1 1 8 Mode switch S2 Run 0 Analog outputs 00 03 X1 Digital output status LEDs L4 L11 Digital outputs 00 03 X5 Analog outputs 04 07 X2 Digital outputs 04 07 X6 To...

Page 11: ...8 are wired in a chain 6 5 3 Adjusting the device address with switch S1 Select the desired device address with this switch by turning it into the right position wit a small screw driver Valid addres...

Page 12: ...annel 0 Channel 4 3 Channel 0 Channel 4 4 Channel 1 Channel 5 5 Channel 1 Channel 5 6 Channel 2 Channel 6 7 Channel 2 Channel 6 8 Channel 3 Channel 7 9 Channel 3 Channel 7 10 Shield Shield Digital out...

Page 13: ...al output inactive log 0 n 0 07 6 5 8 Service interface connector X12 A 9 pin D SUB port found on the bottom side of the device may be used to load new firmware for the device New firmware is loaded v...

Page 14: ...The analog output 0 Ana Out 0 is used for parameteriza tion The 2 parameters are coded in the following way within the 16 bit data word of Ana Out 0 The lower byte D0 D7 contains the pre delay P_DLY...

Page 15: ...igger pulses of Bin Out 0 are ignored Figure 2 Pulse diagram Remarks concerning pulse generator accuracy The accuracy of the programmed pulse length is 6 s for max total sequence length of 51 ms Note...

Page 16: ...FOB card output There are 8 valid device addresses 1 8 The device address is independent from the position of the device within the chain Figure 3 Single daisy chain with ibaPADU 8 O 8 2 Multiple dais...

Page 17: ...ndancy With the ibaBM FOX i 3o device optical data streams fibers may be multiplied This is possible at every location within an input or output chain of ibaPADU devices that means between ibaPADU 8 O...

Page 18: ...in the output resources 3 consists of 32 output sig nals 1 fiber optic output port of an ibaFOB card can transmit 64 signals According to the order of boards in the PC 7 segment display the modules 1...

Page 19: ...4 of device 2 ibaFOB IO O M1 Ana12 The activated binary output is output 1 of device 5 connected with output 2 of ibaFOB IO card with the ID 1 The output data format for the ibaPADU 8 O is always sig...

Page 20: ...ibaFOB IO OUT output channel num ber are always closely related Each of the 3 3 Mbit s output links of an ibaFOB card transmits up to 64 analog and 64 digital signals A daisy chain consisting of up to...

Page 21: ...g which opens automatically you can enter a group name if you want If only the outputs should be assigned select Outputs only in the Directions drop down list If inputs and outputs are needed e g in c...

Page 22: ...Manual ibaPADU 8 O 22 Issue 1 9 In the program designer the sample application of chapter 9 2 would look like as fol lows...

Page 23: ...300 mA 20 with analog load 10 mA channel Typical 220 mA without load FO cable Coupling 62 5 125 m ST Lean Watchdog Communication failure watchdog 20 ms Max length of optical cable without re peater 6...

Page 24: ...signal log 0 0 V log 1 24 V Load power supply external DC 24 V Save state is log 0 Output current output 100 mA typ 250 mA max At 24 V and switching frequency 1000 Hz Short circuit protection Protecte...

Page 25: ...ibaPADU 8 O Manual 11 4 Dimensional drawing Dimensions given in mm Figure 8 Dimension drawing Issue 1 9 25...

Page 26: ...uire support specify the serial number iba S N of the product Contact Headquarters iba AG Koenigswarterstr 44 90762 Fuerth Germany Phone 49 911 97282 0 Fax 49 911 97282 33 E Mail iba iba ag com Contac...

Reviews: