Manual
ibaMS8xAI-110VAC
28
Issue 1.4.1
Figure 16: Editing Off-task connector
Meaning of the default values for the anti-aliasing filter:
FALSE
switched-off
TRUE
switched-on
Now, connect the OTC and the signal on the margin of the programming surface.
Figure 17: Connecting Off-task connector
The configuration of the following functions is similar to the analog filter configuration as
described above. The meaning of the parameters in detail:
Digital anti-aliasing filter
(DigitalFilterMode)
The digital anti-aliasing filter can only be enabled when sampling rate > 500 Hz.
0: off (default setting)
2: Digital anti-aliasing filter activated (once for all channels)
Data type: DINT
Cutoff frequency of the digital anti-aliasing filter
(AntiAliasingFrequency)
=0: Auto = 1/3 of the sampling rate (default setting)
>0: cutoff frequency in Hz (permissible values: 100 Hz … 0.5*sampling rate)
Data type: LREAL