ibaMS8xAI-110VAC
Manual
Issue 1.4.1
23
Unit
You can enter a unit, the default setting is „V“.
Min
You can define a lower limit for the measuring range. The analog normalized value
of -312 V is assigned to a physical value, e. g. -20 °C.
Max
Here, you can define an upper limit for the measuring range. The analog normal-
ized value of +312 V is assigned to a physical value, e. g. +100 °C.
Filter
You can select the antialiasing filter: Butterworth 4th order 20 kHz.
Active
Enabling/disabling the signal.
You can show or hide more columns via the context menu (click with the right
mouse button in the headline).
9.1.3
„Grid frequency [10Hz..80Hz]“ tab
When grid frequency measuring is enabled, this tab appears additionally.
Figure 12: I/O-Manager ibaMS8xAI-110VAC - Grid frequency [10Hz..80Hz] tab
Name
You can enter a name for the signal and two additional comments (click on the
icon in the Name field).
Unit
Default value is „Hz“.
Interval
You can select the measuring interval via a dropdown menu: