●  Wiring 

 
 
 
 
 
 
 
 
 
 
 
 

Set Value 

Communications speed 

Data Length 

4 Mbps (MECHATROLINK-

17 byte 

10 Mbps (MECHATROLINK-

17 byte 

2 (Set in delivery) 

10 Mbps (MECHATROLINK-

32 byte 

(Note) After the parameter setting, cycle the control power, and return the mode toggle switch on the front of the 

controller to “AUTO” side. 

 

MECHATROLINK-

(

Dedicated for CB Type

)

 

Since MECHATROLINK-III is applicable for the standard servo profile but not for the standard I/O profile, it is 

not applicable for the operation modes for other fieldbus products (such as Full Direct Mode). 
●  Specification

 

Refer to the Instruction Manual (ME0317) 

●  Status LED 

LED 

Color 

Illumination Status 

Explanation 

GN

 

Illuminating 

Receiving CONNECT (connected to master) 

CON 

 

Off 

Connection is not established to master 

OR 

Illuminating 

Illumination flashes when communication alarm or command alarm is 

generated (warning excepted). Illumination turned off when alarm is cancelled 

ERR 

 

Off 

In normal condition (no alarm generated) 

LK1 

GN

 

Illuminating

 

LK2 

GN

 

Illuminating

 

Illumination turns on when physically connected to another device applicable 

for MECHATROLINK-

  (for cable breakage check purpose) 

●  Interface Area 

● Node Address Setting 

Node address can be set with the parameter. 

Set Parameter No. 85 “NADR : Fieldbus Node Address” with using 

the PC software for RC. 

Available range for Setting : 3 to 239 [hex] (setting at delivery : 3) 

 

Data Length Setting 
Establish the setting in Parameter No. 86 “FBRS : Fieldbus 
Communication Speed” in RC PC software considering the data 
length to be used. 

 

Setting Value 

Data Length 

Baud Rate

32 bytes 

1 (at the delivery) 

48 bytes 

100Mbps 

 

●  Electronic Gear Ratio Setting 

Set the electronic gear numerator in Parameter No. 65 “CNUM : Electronic Gear Numerator” and the electronic 
gear denominator in No. 66 “CDEN : Electronic Gear Denominator”. In the RC PC software 
Establish the settings to satisfy the following condition: 

         

Stroke [mm]

           

 

Electronic Gear Ratio Denominator 

 

Ball Screw Lead Length [mm]

                 

 

Electronic Gear Ratio Numerator 

 

●  Pulse Count Direction Setting 

  Set the value in Parameter No. 62 “FPIO : Pulse Count Direction” to be the same as what is set in No. 5 “ORG : 

Home-Return Direction” in the RC PC software. 

(Note)

 

Reboot the power on the controller after the parameter settings are completed, and make sure to put the 
switchover switch on the front face of the controller back to the AUTO side. 

●  Wiring

 

Wiring, please use the MECHATROLINK-

  dedicated cable. 

 

CC-Link IE 

(Except for PCON-CA/CFA, ACON-CA, DCON-CA)

 

●  Specification 

Refer to the CC-Link IE Instruction Manual 
 

●  Status LED 

LED 

Color 

Illumination Status 

Explanation 

Steady Light 

Operation in normal conditions 

GN: RUN 

Off 

Hardware error occurred, Power not supplied 

Steady Light 

Error being occurred (Node Error / Station Number Setting Error)

MS 

OR: ERR 

Off 

Operation in normal conditions, Power not supplied 

Steady Light 

Cyclic transmission in process 

Blinking 

Cyclic transmission paused 

GN: D LINK 

Off 

Cyclic transmission not conducted, parallel off, Power not supplied

Steady Light 

Received data in error (Lightened up together with L.ER)

NS 

OR: L ERR 

Off 

Received data in normal conditions, Power not supplied 

Steady Light 

Linkup in process 

LINK 

GN 

Off 

Link-down in process, Power not supplied 

Steady Light 

Received data in error 

L.ER 

OR 

Off 

Received data in normal conditions, Power not supplied 

 
 

●  Interface Area

 

 
 
 

Connector 

Name 

CC-Link IE Connector 

Remarks 

Cable Side 

Ethernet ANSI/TIA/EIA-568-B Category 5e and above 
8P8C modular plug equipped with shield (RJ45) 

Please prepare 
separately 

Controller 
Side 

Ethernet ANSI/TIA/EIA-568-B Category 5e and above 
8P8C modular Jack equipped with shield (RJ45) 

 

 

Pin No. 

Signal Name 

Description 

Applicable cable diameter

1

TP0+

Data 0+

2

TP0-

Data 0-

3

TP1+

Data 1+

4

TP2+

Data 2+

5

TP2-

Data 2-

6

TP1-

Data 1-

7

TP3+

Data 3+

8

TP3-

Data 3-

It is recommended to 
prepare a straight STP cable 
in Category 5e or above for 
the Ethernet cable. 

●  Wiring

 

 
 
 

 

 

 

 

 

 

 

 

 

 
 

Starting Procedure

 

When using this product for the first time, make sure to avoid mistakes and incorrect wiring by referring to 
the procedure below 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

●  Node Address Setting 

The node address is set using specific parameters. 

Set the parameter No.85 “NADR: Fieldbus Node 
Address” using the personal computer application 
software for RC. 
Settable Range : 61 to 7F [hex] 
(It is set to “61” when the machine is delivered from 
the factory.) 

●  Communication Speed Setting 

Set the parameter No.86 “FBRS: Fieldbus 
Communication Speed” using the personal computer 
application software for RC. 

Manual No.: ME0303-7A

Check of Packed Items 
Are there all the delivered items? 

No 

Contact the sales shop. 

Installation and Wiring 
Install the controller and actuator and perform wiring according  
to the instruction manual and the contents in this book. 

Yes 

Point Check Item 

·

Have you performed the frame grounding (FG) and protective earthing (PE)?

·

Has the noise countermeasure been taken?

Yes 

Operation Mode Setting 
Set it according to the items for the operation modes and functions, and each fieldbus.
(Operation Mode, Station No. and Communication Speed)

Power Supply and Alarm Check 
Connect the personal computer or teaching pendant, set the mode  
change switch to “MANU” side and input the power to each unit. 
Select [Teaching Mode 1 Safety Speed Enabled/PIO Startup Disabled]  
in the personal computer application software or the teaching pendant. 
 

Check Item 
Is the LED indicator 
[ALM] turned OFF on 
the front panel?

No

Yes 

Connect the personal computer or 
teaching pendant and confirm the 
alarm description to treat the problem.

Set the Safety Speed
Set it using the parameter No.35, if necessary.
When the machine is delivered, the safety speed has been set to “100mm/s”.

Servo ON 
Turn ON the servo motor with the personal computer or  
teaching pendant operation. 

Caution

When the machine is turned ON/OFF repeatedly at the same  
position, it might be lowered slightly due to its own weight.  
Take care not to catch your hand or damage the work. 

Check Item 
Does the Status LED Indicator  
[SV] illuminate in green? 

When an alarm is sounded, connect the  
personal computer or teaching pendant  
and confirm the alarm description to treat  
the problem. 

Check of Safety Circuit 

Yes 

Yes 

Yes 

Yes 

Yes 

Check that the emergency stop circuit (or motor drive-power cutoff circuit) 
operates normally to turn OFF the servo.

No 

No 

Check the emergency stop circuit. 

Target Position Setting 
Set a target position in the “Position” field for each position in the position table. 
When carrying out direct teaching, perform home return operation first. 
When the unit is equipped with the brake, move it after setting the brake release switch to “BK RLS” side. 

Caution

To ensure safety, it is recommended  
that safety speed be enabled during  
initial movements. 

Trial Run Adjustment 
(1) Set the safety speed to “Disable” using the personal computer application 
     software or teaching pendant and perform the performance check.
(2) Set the personal computer or teaching pendant to “MANU” operation mode, 
     select the “Monitor Mode 2: Safety Speed Disabled/PIO Start-up Permitted” 
     and then, remove it from the controller.
(3) Set the mode toggle switch to “AUTO”.
(4) Set the fieldbus on the host side.

No 

In the case that vibration or abnormal noise is caused 
Confirm that there is no problem in the actuator  
installation or the actuator operation condition demands  
more than the rated voltage. 

Check Item 
Start up the host side and check if the LED indications on the front panel 
for each fieldbus are as follows.
CC-Link : ERR OFF,  RUN Green Light is turned ON.
DeviceNet, CompoNet, PROFIBUS : Green light is turned ON for both MS and NS.
MECHATROLINK : Green light is turned ON for both STATUS1 and STATUS0.

No 

·

Check the station No. setting.

·

Check the terminal resistance.

·

Check the communication speed setting.

The driving preparation was completed above. Please do the system driving adjustment.

NC

/DATA

DATA

SH

NC

/DATA

DATA

SH

NC

/DATA

DATA

SH

Master

Unit

PCON, ACON, DCON

Terminator
JEPMC-W6022

MECHATROLINK Cable

·

JEPMC-W6002-□□

·

JEPMC-W6003-□□

PCON, ACON, DCON

 

CON

ERR

 

Status LED

 

 
 
 

Upstream Side 
LK1 (link 1)LED 
 
 
 
 
Downstream 
Side 
LK2 (link 2)LED 

×

 No. of Encoder Pulses 

×

   

 

2

31

 

Top View of 

Connector on 

Controller side 

L.ER
 
 
 
LINK

L.ER
 
 
 
LINK

Ethernet Straight Cable    Category 5e or more 
Double shielded cable braided with aluminum foil recommended 
(Note) Terminal resistance is not required 

There is no distinction 
of IN/OUT on the 
connector. 

Master Unit 

Slave Devices 

PCON, ACON, DCON CC-Link IE Type 