DeviceNet
Type
Refer to the instruction manuals for each Field Network master unit and mounted PLC for the details.
Connector Name
DeviceNet Connector
Cable Side
MSTB2.5/5-ST-5.08 ABGY AU
Enclosed in standard
package
Manufactured by PHOENIX
CONTACT
Controller Side
MSTBA2.5/5-G-5.08 ABGY AU
Pin No.
Signal Name
(Color)
Description
Applicable cable diameter
1
V- (BK)
Power Supply Cable Negative Side
2
CAN L (BL)
Communication Data Low Side
3 Shield
(None)
Shield
4
CAN H (WT)
Communication Data High Side
5
V+ (RD)
Power Supply Cable Positive Side
Dedicated cable for
DeviceNet
CC-Link Type
Refer to the instruction manuals for each Field Network master unit and mounted PLC for the details.
Connector Name
CC-Link Connector
Cable Side
MSTB2.5/5-ST-5.08 ABGY AU
Enclosed in standard
package
Manufactured by PHOENIX
CONTACT
Controller Side
MSTBA2.5/5-G-5.08AU
Pin No.
Signal Name
(Color)
Description
Applicable cable diameter
1
DA (BL)
Communication Line A
2
DB (WT)
Communication Line B
3
DG (YW)
Digital GND
4
SLD
Connect the shield of the shielded cable
(Connect the FG of the 5 pins and
controller FG internally)
5
FG Frame
Ground
(Connect the SLD of the 4 pins and
controller FG internally)
Dedicated cable for CC-Link
PROFIBUS-DP
Type
Refer to the instruction manuals for each Field Network master unit and mounted PLC for the details.
Connector Name
PROFIBUS-DP Connector
Cable Side
9-pin D-sub Connector (Male)
Please prepare separately
Controller Side
9-pin D-sub Connector (Female)
Pin No.
Signal Name
Description
Applicable cable diameter
1 NC
Disconnected
2 NC
Disconnected
3
B-Line
Communication Line B (RS485)
4
RTS
Request for Sending
5
GND
Signal GND (Insulation)
6
+5V
+5V Output (Insulation)
7 NC
Disconnected
8 A-Line
Communication
Line
A
(RS485)
9 NC
Disconnected
PROFIBUS-DP Dedicated
Cable
CompoNet Type
Refer to the instruction manuals for Field Network master unit and mounted PLC for the details.
Connector Name
CompoNet Connector
Cable Side
Prepare a connector complied with CompoNet standards.
Controller Side
XW7D-PB4-R
Produced by OMRON
Pin No.
Signal Name
(Color)
Description
Applicable cable diameter
1 BS+
(RD)
Communication Power
(Note 1)
2
BDH (WT)
Signal line H side
3
BDL (BL)
Signal line L side
4 BS-
(BK)
Communication Power Supply -
(Note 1)
CompoNet Dedicated Cable
Note 1 It is not necessary to supply the communication power. (Internal power source is
used.)
If conducting multi power supply to other slave devices via communication
cables, there is no problem with connecting the power supply to BS+ and BS-
terminals.
EtherNet/IP Type
Refer to the instruction manuals for Field Network master unit and mounted PLC for the details.
Connector Name
EtherNet/IP Connector
Cable Side
8P8C Modular Plug
Controller Side
8P8C Modular Jack
Pin No.
Signal Name
Description
Applicable cable diameter
1
TD+
Data s
2
TD-
Data sending -
3
RD+
Data rec
4 –
Disconnected
5 –
Disconnected
6
RD-
Data receiving -
7 –
Disconnected
8 –
Disconnected
For EtherNet cable, use a
straight STP cable that
possesses the performance of
Category 5e or more.
EtherCAT Type
Refer to the instruction manuals for Field Network master unit and mounted PLC for the details.
Connector Name
EtherCAT Connector
Cable Side
8P8C Modular Plug
Controller Side
8P8C Modular Jack
Pin No.
Signal Name
Description
Applicable cable diameter
1
TD+
Data s
2
TD-
Data sending -
3
RD+
Data rec
4 –
Disconnected
5 –
Disconnected
6
RD-
Data receiving -
7 –
Disconnected
8 –
Disconnected
For EtherNet cable, use a
straight STP cable that
possesses the performance of
Category 5e or more.
1
2
3
4
5
Front View of
Connector on
Controller side
1
2
3
4
5
Front View of
Connector on
Controller side
Shield
BL (CAN L)
RD (V+)
WT (CAN H)
BK (V-)
WT (DB)
BL (DA)
Shield (SLD)
YW (DG)
Slave Devices
MSEP-DeviceNet Type
V+
Drain
(Shield)
CAN_H
CAN_L
V-
RD
WT
BL
BK
RD
WT
BL
BK
V+
Drain
(Shield)
CAN_H
CAN_L
Class D grounding
(Formerly Class-III grounding: Grounding resistance at 100
Ω
or less)
V+
Drain
(Shield)
CAN_H
CAN_L
V-
RD
WT
BL
BK
Communication power needs to be
supplied by an external device.
Terminal Resistance is required
to be mounted on the terminal.
V-
Terminal Resistance
121
Ω
Master Unit
Terminal Resistance
121
Ω
24V
Power Supply
Slave Devices
MSEP-
CC-Link
Type
SLD and FG are internally connected.
Terminal Resistance is required
to be mounted on the terminal.
The terminal resistor differs depending on the type
of the dedicated cable for CC-Link.
• Cable FANC-SBH···130
Ω
1/2W
(High Performance Cable
dedicated for CC-Link)
• Cable FANC-SB······110
Ω
1/2W
(CC-Link Dedicated Cable)
Master Unit
Terminal
Resistance
Terminal
Resistance
Class D grounding
(Formerly Class-III grounding:
Grounding resistance at 100
Ω
or less)
5 1
9 6
Cable
Shield
Red B line (Positive side)
Green A line (Negative side)
1
6
9
5
Front View of
Connector on
Controller side
BK (BS-)
BL (BDL)
RD (BS+)
WT (BDH)
Front View of
Connector on
Controller side
1
2
3
4
8
1
8
1
Front View of
Connector on
Controller side
Master Unit
Switching Hub
Slave Devices
EtherNet Straight Cable, Category 5e or more
Double shielded cable braided with aluminum foil
recommended
MSEP- Unit
EtherNet/IP Type
Master Unit
Slave Devices
EtherNet Straight Cable
Category 5e or more
Double shielded cable braided with aluminum
foil recommended
(Note) Terminal resistance is not required
1
8
Front View of
Connector on
Controller side