32
11. TECHNICAL SPECIFICATIONS
Electrical Ratings:
Control:
110-240VAC
5VA AC or 5W DC
Range: -45% to + 10%
(60-264V
AC/DC)
Output Relay Contacts:
Main Trip Relay:
Type: Form Z (NO and NC Pair)
Rating: 10A @ 240VAC
10A @ 30VDC
1/2 HP @ 240VAC
Auxiliary Ground Fault Relay:
Type: 1 Form C (NO/NC)
Rating: 10A @ 240VAC
8A @ 24VDC
1/2 HP @ 240VAC
Auxiliary NGR Fault Relay:
Type: 1 Form C (NO/NC)
Rating: 10A @ 240VAC
8A @ 24VDC
1/2 HP @ 240VAC
All relays are electrically held and are de-energized
when control power if OFF.
Failsafe: When the failsafe option is ON, the trip relay is
normally energized when control power is ON and is
de-energized in a trip state. When in shunt trip mode,
the trip relay is normally de-energized when control
power is ON and is energized in a trip state.
Figure 11.1: Dimensional Drawings