background image

The green LED indicates two functions: When slow flashing it means control power is applied to terminals N- and L+; 

when fast blinking it denotes the relay has sensed a ground fault current higher than the trip level threshold selected 
for a period longer than the tripping time delay and that the output contacts have operated.

The mGARD-100 operates on any control voltage from 40 to 240V AC or DC, and contains an isolated power supply. 

The seven position terminal block is pull-apart type that eases the wiring in the field.

A three position, pull-apart terminal connects the relay to the mGARD-SYM remote indicator (with modbus 
connectivity) for remote test / reset and monitoring.

Special consideration must be taken in the selection of the neutral grounding resistor in a high resistance grounded 
system as the capacitance-to-ground charging current on a system will vary depending on: the overall length of the 
cables; the types of loads; the quality of insulation on the phase conductors; the surrounding equipment grounding, 

cable trays, junction boxes, the type of sensor, etc. A “Rule-of-Thumb” for systems 600V and lower: The charging 
current is 0.5 Amps per 1000 kVA of sensor capacity. In electrical systems of 600V and below it is common to use a 

5 Ampere continuous rating for the neutral grounding resistor and setting the pickup current at 20% of that value (1 
Ampere) for all relays and coordinating between upstream and downstream relays by selecting different time delays.

3. OpERATION

3.1 OPERATION AND GLOSSARY OF TERMS

Auto Reset:

After a trip, the relay will automatically reset itself three seconds after the ground fault current drops below the trip 
current set point. The auto reset feature can be used in both failsafe and non-failsafe modes.

Chassis Ground:

Chassis ground is the ground to which all of the non-current carrying metal equipment is connected/bonded. 

Typically, equipment grounding is provided by means of a ground bus. A solid connection is to be made from 
terminal 7 of the mGARD-100 to the nearest chassis ground to ensure the relay complies with the specified 
electromagnetic compatibility (EMC) standards. If using an external zero sequence current sensor, do not ground 
any of the ZSCS secondary wires.

Interposing Current Sensor:

Interposing Zero Sequence Current Sensors (ZSCS) are required for any of the following applications:

• The ground fault trip current setting levels are higher than the 30 mA –12 Amp range available with the built-in 

2” ZSCS.

• The size of the power conductors on which the mGARD-100 is being applied is too large for the 2” built-

in ZSCS.

• The system primary phase current on which the mGARD-100 is being applied exceeds 250 Amps continuous.

Failsafe:

The output relay changes state when control power is applied to terminals N- & L+. The N.O. contact closes and 

the N.C. contact opens. When a trip occurs or control voltage is removed, the N.O. contact is opened and the N.C. 
contact is closed.

Summary of Contents for mGARD-100

Page 1: ...C 419EM Instruction Manual March 2015 Ground fault relay microprocessor based relay mGARD 100...

Page 2: ...mer service and technical leadership We build on this foundation by investing in developing new products in electrical safety education including EFC scholarship program by actively participating in t...

Page 3: ...safe 4 Manual Rreset 4 3 2 Dipswitch Settings 4 3 3 Indication 6 mGard Sym Remote Indicator 6 3 4 Reset 7 3 5 Ground Fault Test 7 4 Installation Instructions 8 4 1 Mounting 8 4 2 Built In Current Tran...

Page 4: ...nate false tripping when using the relay on systems with variable frequency drives With the harmonic filter disabled the relay will accurately respond to AC currents between 25 and 400Hz By using an i...

Page 5: ...mpere for all relays and coordinating between upstream and downstream relays by selecting different time delays 3 operation 3 1 Operation and Glossary of Terms Auto Reset After a trip the relay will a...

Page 6: ...s set to trip the relay contacts change their state Time Delay Intentional period of time programmed to elapse before the tripping operation of the relay It should not be confused with the breaking op...

Page 7: ...L R R R R L L R R L R R R R L R R R R 30 40 60 90 150 250 400 600 900 1500 2500 4 6 9 10 12 3 4 6 9 15 25 40 60 90 150 250 400 600 900 1000 1200 30 40 60 90 150 250 400 600 900 150 250 4000 6000 9000...

Page 8: ...t Trip LED Steady On Control voltage too low or mGARD 100 defective MGARD SYM REMOTE INDICATOR The mGARD SYM is a remote display indicator that is used in conjunction with I Gard relays The indicator...

Page 9: ...t is NOT necessary to press the remote test reset button after the ground fault has been cleared when the mGARD 100 is set in the pulsed trip auto reset mode In this mode the relay will reset automati...

Page 10: ...ing current sensor keep the distance between the relay and the sensor as short as possible Use twisted cable and increase the gauge of the conductor as per the table below Table 4 0 ZSCS secondary wir...

Page 11: ...4 Cables in form factor 2 42 mm 0 3 0 34 0 43 0 59 0 75 0 87 1 02 7 74 8 7 11 15 19 22 26 6 7 Cables in form factor 3 0 mm 0 37 0 43 0 54 0 73 0 93 1 07 1 26 9 6 10 8 14 18 24 27 32 9 10 Cablse in fo...

Page 12: ...phase and neutral conductors through the window of the interposing zero sequence current sensor Note that the relay is located downstream from the neutral ground point Position the cable in the centre...

Page 13: ...shows an mGARD 100 relay operating in non failsafe mode The relay is monitoring the neutral conductor in a resistance grounded system Figure 4 3 shows a system with several mGARD 100 relays monitoring...

Page 14: ...listed below in Table 5 1 Table 5 1 mGARD 100 DC control voltage options 12V 9 18 VDC 12DCV mGARD 100 12DCV 24V 18 36 VDC 24DCV mGARD 100 24DCV dc voltage range catalogue number suffix example 6 serv...

Page 15: ...ts Main Trip Relay Type Form Z N O and N C pair Rating 10A 250V AC resistive 10A 30V DC resistive Terminal Contact Material Clamping screw nickel plated brass Plug contacts tin plated bronze Physical...

Page 16: ...I GARD RESERVES THE RIGHT TO CHANGE SPECIFICATIONS OF ITS PRODUCTS WITHOUT NOTICE 8 dimensional drawings Figure 8 0 mGARD 100 dimensions in millimetres inches...

Page 17: ...Notes...

Page 18: ...www i gard com Phone 905 673 1553 Toll Free 1 888 737 4787 Fax 905 673 8472 sales i gard com...

Reviews: