background image

I-GARD         GCHK-100 Instruction Manual

4

5

 remote indication

gHCK-drI

 

A simple remote indicator is available as an option, which provides indication of the status of the GCHK-100. 
The GCHK-DRI has all three status lights that are normally visible on the GCHK-100 as well as a reset button. 
This allows the relay to be monitored conveniently and RESET if necessary. The relay may also be tested by 
pressing the RESET/TEST button twice quickly. 

The GCHK-DRI is flush-mounted in a panel with four ½ in x 6-32 screws with nuts. A rectangular opening of 82 x 
51 mm (3 1/4 x 2 in) is required for mounting as shown in Figure 11.3. 

  A 5-conductor cable with 22 gauge or larger conductors may be used to connect the GCHK-DRI to the  

GCHK-100 relay. No shielding is required. No additional power supply is required to power the indicator. 

Figure 5.1 shows the faceplate of the GCHK-DRI. This simple indicator extends the 3 red LED’s and yellow push 
button on the GCHK-100 to a panel or remote location. Press the yellow button once to reset the relay or twice 
quickly to test (Warning: a test will cause the GCHK-100 to trip).

Figure 5.1 GCHK-DRI label

mgard-SYM 

The mGARD-SYM is a remote display indicator that is used in conjunction with I-Gard Corp. relays. The 
indicator has the capability to interconnect with up to 50 GCHK-100 relays in a bus network topology and 
provides detailed device status information. 

The display has a 4-line screen that shows a list of connected devices. A device can be selected and viewed in 
detail. The relay mode, delay and trip level settings can be viewed (but not altered). The reset and test functions 
can be performed directly from the display. 

Fault levels are displayed as a percentage of the selected trip level. If the trip level is 1 Amp and there is a  
500 mA fault current, the reading on the display will appear as 50%. Ground check resistance and frame voltage 
are also displayed as a percentage of the trip setting. Screen navigation is done using a 4-button interface.  
The menus are displayed on the right side of the LCD, the left side is reserved for viewing relay information. 

Summary of Contents for GCHK-100

Page 1: ...Instruction Manual C 407 ground fault protection SYSTEM GCHK 100 GCHK 100 mining relay the power to protect...

Page 2: ...ed are not to be installed immediately they should be stored in their original packaging in an area free of dust and moisture important In our continuing effort to bring new and innovative products to...

Page 3: ...el 5 Figure 6 1 Connection Diagram 6 Figure 11 1 GCHK 100 Main Relay Outline Dimensions inches 14 Figure 11 2 mGARD SYM LCD Remote Indicator Dimensions inches 15 Figure 11 3 GCHK DRI LED Remote Indica...

Page 4: ...cation Ground Fault detection requires the use of current sensors and the GCHK 100 is designed to operate with I Gard TxA type sensors or a wide variety of sensors with ratios of 1000 1 600 1 and 40 1...

Page 5: ...Startco Surge protection is built into the relay please refer to the electrical specifications data for withstand ratings ZSCS with or without built in protection can be used with the GCHK 100 relay...

Page 6: ...00 to a panel or remote location Press the yellow button once to reset the relay or twice quickly to test Warning a test will cause the GCHK 100 to trip Figure 5 1 GCHK DRI label mGARD SYM The mGARD S...

Page 7: ...status and fault levels as well as remote reset For more information on the mGARD SYM display refer to the mGARD SYM manual C 416EM R0 6 INSTALLATION Mounting The main unit of the GCHK 100 is supplie...

Page 8: ...nding on the ratio of the chosen sensor All phases supplied to the trailing cable must pass through the window of the ZSCS which must be sized accordingly I Gard sensors range from 2in to 9in in diame...

Page 9: ...See Table 7 1 Normal mode is with a non energized TRIP relay which becomes energized when the trip level is exceeded for a duration exceeding the selected time delay Alternatively the FAILSAFE mode ca...

Page 10: ...s Function Setting 1 2 3 4 5 6 7 Switch2 0 25A 0 0 0 0 Ground Fault 0 25 A 0 0 0 0 Pickup 0 5 A 0 0 0 X Settings 0 75 A 0 0 X 0 IG 1 A 0 0 X X 1 25 A 0 X 0 0 1 5 A 0 X 0 X 2 A 0 X X 0 2 5 A 0 X X X 3...

Page 11: ...ter begins to time the trip interval If the ground fault disappears for the duration specified in the table below or more the timer is reset and the relay does not trip Table 7 4 Ground Fault Delay Re...

Page 12: ...ed in the operation of the GCHK 100 relay to detect if the frame to ground voltage of the mobile equipment has exceeded preset levels The voltage detection will operate within 100 ms quicker than the...

Page 13: ...g regular switchboard maintenance DANGER Hazard of Electrical Shock Burn or Explosion All installation servicing and testing referred to in this manual must be performed by qualified personnel All pow...

Page 14: ...ays but one way is to apply a test fault resistor to the system with the oscilloscope connected to a current transformer arranged to measure fault current The Delay time will be the time that the curr...

Page 15: ...e 20 or 3 Ohms Delay for open loop and or shorted terminator 150 ms to 300 ms Fuse Amp time delay Bussman FNQ LittelFuse FLQ Edison MEQ Operating Mode Manual Reset or Auto Reset Induced AC Withstand 3...

Page 16: ...I GARD GCHK 100 Instruction Manual 14 11 OUTLINE DIMENSIONS Figure 11 1 GCHK 100 Main Relay Outline Dimensions inches 5 50 0 20 0 25 3 50 0 19 4 20 5 90 4 00 0 15 4 72...

Page 17: ...ote Indicator Dimensions inches 5 16 5 16 2 15 3 94 3 94 0 41 3 94 3 94 0 41 Figure 11 3 GCHK DRI LED Remote Indicator Dimensions inches 4 34 0 35 3 87 0 61 0 26 0 64 3 05 1 92 0 14 1 18 2 29 4 34 2 2...

Page 18: ...I GARD GCHK 100 Instruction Manual 16 Figure 11 4 GCHK ZT Zener Diode Line Terminator Outline Dimensions inches 1 16 2 65 1 38 0 19...

Page 19: ...RM Sigma Resistor Monitoring and Ground Fault Relay C 322 MGFR Ground Fault Relay Manual C 409 DSP Ohmni High Resistance Grounding System Manual C 102 Gemini High Resistance Grounding System Manual C...

Page 20: ...the power to protect...

Reviews: