The condition and process of dehumidifying
If T
amb
>T
set
+2
℃
, DRY mode will act. The compressor and the outdoor fan will run, and indoor
fan will run at low speed.
If T
set
-2
℃
≤
T
amb
≤
T
set
+2
℃
, DRY mode will act. The indoor fan will run at low speed. The
compressor and outdoor fan stop six minutes after it is started, and restart four minutes later.
Process of dehumidifying runs circularly as above.
If T
amb
<T
set
-2
℃
, the compressor and the outdoor fan will stop running, and the indoor fan will run
at low speed.
¾
In this mode, the four-way valve will not be powered on and the temperature setting range is
16 ~30
℃
. Monitor displays running symbol, dehumidifying symbol and set temperature.
②
Protection function
◆
Antifreezing protection
In cooling by dehumidifying mode, when the antifreezing protection is detected, the compressor
and the outdoor fan will stop running, and the indoor fan will keep running at low speed. When
antifreezing protection is eliminated and the compressor has stopped for 3 minutes, the whole unit
will resume running in the original mode. Six minutes’ starting and four minutes’ stop shall be
met. When the antifreezing protection is detected, the compressor and the outdoor fan will stop
running, and the indoor fan will keep running at low speed. When antifreezing protection is
eliminated and the compressor has stopped for 4 minutes, the whole unit will resume running in
the original mode.
③
Other protection
Other protection is same with that in COOL mode.
(3) Heat mode ( single cooler wihout this mode)
①
The condition and process of heating
If T
amb
≤
T
set
+2
℃
, Heat mode will act. The four-way valve, compressor and outdoor fan will run
at the same time. The indoor fan will delay two minutes to run at the latest.
If T
amb
≥
T
set
+4
℃
, the compressor, outdoor fan and four-way valve will be powered on
continuously. The indoor fan will stop after it blows at the set speed for 60 seconds.
If T
set
+2
℃<
T
amb
<
T
set
+4
℃
, the unit will keep running in the current state.
¾
In this mode, the temperature setting range is 16 ~30
℃
. The monitor displays running
symbol, heating symbol and set temperature.
Cooling runs
Dehumidifying runs
Stop running
Run
Stop
Low fan speed
Compressor
Outdoor fan
Indoor fan
T
set
+2
℃
T
set
-2
℃
T
amb
6 min
4 min
6 min
183
Summary of Contents for HSH-121NBE
Page 1: ......
Page 2: ......
Page 3: ...1 ...
Page 46: ...44 ...
Page 69: ...7 3 Exploded View of Components and Parts of Indoor unit 67 ...
Page 70: ...7 4 Exploded View of Components and Parts of Indoor unit 68 ...
Page 72: ...7 5 Exploded View of Components and Parts of Indoor unit 70 ...
Page 73: ...7 6 Exploded View of Components and Parts of Indoor unit 71 ...
Page 74: ...7 7 Exploded View of Components and Parts of Indoor unit 72 ...
Page 75: ...7 8 Exploded View of Components and Parts of Indoor unit 73 ...
Page 77: ...7 9 Exploded View of Components and Parts of Indoor unit 75 ...
Page 78: ...7 10 Exploded View of Components and Parts of Indoor unit 76 ...
Page 79: ...7 11 Exploded View of Components and Parts of Indoor unit 77 ...
Page 80: ...7 12 Exploded View of Components and Parts of Indoor unit 78 ...
Page 81: ...7 13 Exploded View of Components and Parts of Indoor unit 79 ...
Page 83: ...7 14 Exploded View of Components and Parts of Indoor unit 81 ...
Page 84: ...7 15 Exploded View of Components and Parts of Indoor unit 82 ...
Page 85: ...7 16 Exploded View of Components and Parts of Indoor unit 83 ...
Page 86: ...7 17 Exploded View of Components and Parts of Indoor unit 84 ...
Page 87: ...7 18 Exploded View of Components and Parts of Indoor unit 85 ...
Page 88: ...7 19 Exploded View of Components and Parts of Indoor unit 86 ...
Page 89: ...7 31 Exploded View of Components and Parts of Outdoor unit 87 ...
Page 91: ...7 32 Exploded View of Components and Parts of Outdoor unit 89 ...
Page 93: ...7 33 Exploded View of Components and Parts of Outdoor unit 91 ...
Page 95: ...7 34 Exploded View of Components and Parts of Outdoor unit 93 ...
Page 96: ...Trouble Shooting Trouble Shooting 8 94 ...
Page 97: ...95 ...
Page 98: ...96 ...
Page 102: ...Outdoor Unit For 24K 100 ...
Page 103: ...Outdoor Unit For 30 36K 101 ...
Page 110: ...108 ...
Page 111: ...109 ...
Page 113: ...Make sure whether the outlet air temperature subtract from inlet sgives more than 10 111 ...
Page 114: ...HEALTH SLEEP FEELING POWER TIMER CLOCK 112 ...
Page 133: ...Intelligent Defrost Unit have no Temperature Sensor Outdoor unit 131 ...
Page 144: ...dehumidifying mode and the indoor fan motor slows down exchanger from being frozen 142 ...
Page 150: ...8 The Failure Analysis of the Main Parts 148 ...
Page 151: ... 3 Indoor unit exploded picture 24 36 BTU S Series 149 ...
Page 153: ... 4 Outdoor unit exploded picture 36K BTU S Series 151 ...
Page 163: ...App3 Current Wiring Diagram of PCB Non Inverter 3 1 161 ...
Page 164: ...3 2 162 ...
Page 166: ...3 4 164 ...
Page 167: ...3 5 165 ...
Page 168: ...166 ...
Page 169: ...Normal panel Mirror panel 167 ...
Page 170: ...168 ...
Page 171: ...Note only 09 12 outdoor fan is explained as example for outdoor fan 169 ...
Page 172: ...170 ...
Page 173: ...above 7cm above 7cm above 20cm 171 ...
Page 174: ...172 ...
Page 175: ...173 ...
Page 191: ...189 ...
Page 192: ...190 ...
Page 193: ...191 ...
Page 194: ...192 ...
Page 195: ...193 ...
Page 196: ...194 ...
Page 197: ...195 ...
Page 198: ...196 ...
Page 199: ...197 ...
Page 200: ...198 ...
Page 201: ...199 ...
Page 202: ...200 ...
Page 203: ...201 ...
Page 204: ...202 ...
Page 205: ...203 ...
Page 206: ...204 ...
Page 207: ...205 ...
Page 208: ...206 ...
Page 209: ...207 ...
Page 210: ...208 ...
Page 211: ...209 ...
Page 212: ...210 ...
Page 213: ...211 ...
Page 214: ...212 ...
Page 215: ...213 ...
Page 216: ...214 ...
Page 217: ...215 ...
Page 218: ...216 ...
Page 219: ...217 ...
Page 220: ...218 ...
Page 221: ...219 ...
Page 222: ...220 ...
Page 223: ...221 ...
Page 224: ...222 ...