background image

 

IM2021 

 

32 

 

–  Marking  to  the  equipment  continues  to  be  visible  and  legible.  Markings  and  signs  that  are 
illegible shall be corrected; 

–  refrigeration  pipe  or  components  are  installed  in  a  position  where  they  are  unlikely  to  be 
exposed  to  any  substance  which  may  corrode  refrigerant  containing  components,  unless  the 
components are constructed of materials which are inherently resistant to being corroded or are 
suitably protected against being so corroded. 

8. 

Checks to electrical devices 

Repair  and  maintenance  to  electrical  components  shall  include  initial  safety  checks  and 
component  inspection  procedures.  If  a  fault  exists  that  could  compromise  safety,  then  no 
electrical  supply  shall  be  connected  to  the  circuit  until  it  is  satisfactorily  dealt  with.  If  the  fault 
cannot  be  corrected  immediately  but  it  is  necessary  to  continue  operation,  an  adequate 
temporary  solution  shall  be  used.  This  shall  be  reported  to  the  owner  of  the  equipment  so  all 
parties are advised. 
Initial safety checks shall include: 
-those  capacitors  are  discharged:  this  shall  be  done  in  a  safe  manner  to  avoid  possibility  of 
sparking; 
-that  there  no  live  electrical  components  and  wiring  are  exposed  while  charging,  recovering  or 
purging the system; 
-that there is continuity of earth bonding 

9. Maintenance of sealed components 

It is important to ensure that all  power sources are disconnected from the operating equipment 
during the maintenance of sealed components, before removing the sealing covers, etc. 
In  case  of  necessity  to  provide  power  to  the  equipment  during  maintenance,  it  is  important  to 
provide  a  permanent  leak  detection  system  at  the  most  critical  point  in  order  to  warn  of  a 
potentially dangerous situation. 
Pay particular attention to ensure the impossibility to change/damage/deform the housing when 
working  with  electrical  components  in  such  a  way  as  to  affect  the  protection  level,  namely: 
damage  to  cables,  excessive  number  of  connections,  non-compliance  of  terminals  with  the 
original specification, damage to seals, improper installation of oil seals, etc. 
Make sure that the device is installed in a secure manner. 
Make sure that the seals or sealing materials are not worn to such an extent that they no longer 
prevent the passage of flammable substances. Spare parts shall comply with the manufacturer's 
specifications. 

NOTE:

 The use of silicone sealant can reduce the effectiveness of some types of leak detection 

equipment. Intrinsically safe components do not have to be isolated before working on them. 

10. Maintenance of intrinsically safe components 

Before  applying  permanent  inductive  or  capacitive  loads  to  the  circuit,  ensure  that  they  do  not 
exceed the permissible voltage and current allowed for the equipment. 
Structurally  intrinsically  safe  components  shall  be  the  only  type  of  equipment  that  can  be 
operated under voltage in case of a flammable atmosphere. The test equipment shall be of the 
appropriate class. 
The components shall only be replaced with the parts specified by the manufacturer. Other parts 
may ignite the cooling agent in the atmosphere due to its leakage. 

11. Wiring 

Make sure the cables are not exposed to wear, corrosion, overpressure, vibration, damage due 
to contact with sharp edges, or any other adverse environmental effects. Take into account also 
the  effects  of  wear  from  physical  obsolescence  or  constant  vibration  from  such  sources  as 
compressors or air fans. 

12. Flammable cooling agents leak detection 

Do not use appliances that can be a potential source of ignition when searching for or detecting 
cooling agent  leaks  under  any  circumstances.  The  use  of halogen leak  detectors  (or  any  other 
means of open flame detection) is prohibited. 

13. Leak detection methods 

The following leak detection methods shall be considered as acceptable for systems containing 
highly flammable cooling agents. 
In  order  to  detect  flammable  cooling  agents,  use  electronic  leak  detectors,  however,  the 
sensitivity may be insufficient or recalibration may be required (the detection equipment shall be 

Summary of Contents for H-DH16-P82WF

Page 1: ...INSTRUCTION MANUAL ELECTRIC DEHUMIDIFIER H DH16 P82WF...

Page 2: ...IM2021 2 1 2 1 R290 2 3 4 5 6 7 8 8...

Page 3: ...IM2021 3 9 10 11 12 13 0 C 2 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 4 2 29 30 31 32 33 34 35 36...

Page 4: ...IM2021 4 37 38 39 40 41 42 43 44 20 45 46 3 4 1 1 H DH16 P82WF 16 2 270 220 240 50 1 4 3 110 38 R290 Class I...

Page 5: ...IM2021 5 50 0 7 3 2 5 35 2 20 30 12 13 280x200x500 5 1 2 3 4 5 6 7 8 9 10 11 12 13 1...

Page 6: ...IM2021 6 6 4 2 20 5 41 F 2...

Page 7: ...IM2021 7 5 41 F 35 95 F 220 240 50 7 1 1 2 1 3 1 4 1 8 30...

Page 8: ...IM2021 8 3 3 30 to 35 40 45 50 55 60 65 70 75 80 30 3 0 24 1 1 00...

Page 9: ...IM2021 9 57 30 63 9 WI FI Wi Fi Smart Life Android iOS 4G Wi Fi iOS 8 0 Android 4 4 2 4 Smart Life...

Page 10: ...IM2021 10 QR code Smart Life 5 Wi Fi Wi Fi AP Wi Fi SmartLife XXXX Wi Fi 5 Wi Fi 1 Wi Fi SmartLife XXXX 2 10 Wi Fi 10 Wi Fi Wi Fi 10...

Page 11: ...IM2021 11 10 1 2 3 4 5 6 7...

Page 12: ...IM2021 12 1 2 11 1...

Page 13: ...IM2021 13 2 3 4 12 1 2 3 4 13...

Page 14: ...IM2021 14 1 2 3 4 CO2 5 6...

Page 15: ...IM2021 15 7 8 9 10...

Page 16: ...IM2021 16 11 12 13 OFN 14 OFN OFN OFN...

Page 17: ...IM2021 17 15 OFN 16 a b c d e f g 80 h i j 17 18...

Page 18: ...IM2021 18 14 2 2 5 C 35 C...

Page 19: ...IM2021 19 E2 LO 20 HI 90 CL 5 CH 38 15...

Page 20: ...ety precautions must be observed Improper operation by ignoring safety precautions can result in damage to the health of the user and other people as well as damage to their property 1 The unit is des...

Page 21: ...e This may cause an electric shock or damage to the device 28 Install operate and store the device in a room with an area of more than 4 m 2 29 Store the device in a well ventilated place The non vent...

Page 22: ...P82WF Dehumidification capacity l d 16 Volume of the tank l 2 Rated power consumption W 270 Power Options V Hz 220 240 50 Rated current 1 4 Air consumption m 3 h 110 Noise level Internal External Spl...

Page 23: ...al instrument 6 INSTALLATION WARNING Install the unit in rooms which exceed 4 m Do not install the unit in a place where inflammable gas may leak Do not use in the outdoors This dehumidifier is intend...

Page 24: ...elected when the unit was last used Check the device after unpacking for any damages or scratches on it Select a suitable location making sure that there is easy access to an electrical outlet Connect...

Page 25: ...mpressor starts working after 3 seconds When environmental humidity set humidity 3 the compressor stops working and fan stops working after 30 seconds delay Both fan speed and humidity can be adjusted...

Page 26: ...de Long press to turn on off the child lock function Touch the sleep button the sleep indicator will light up the mode indicator will go out and the wind speed will automatically change to low wind to...

Page 27: ...I long press the timer button for 5 Second to start the network configuration the WIFI indicator flashes slowly 6 When WIFI indicator flashes slowly select Add Device Small Home Appliances Dehumidifie...

Page 28: ...heck that the float is correctly in place WARNING Do not discard water tank magnets and plastic rivets Otherwise the machine will not automatically stop working when the water tank is full and the con...

Page 29: ...nd the drain pipe The height of the drain pipe should be lower than the outlet The drain pipe shall be securely connected to the outlet 11 MAINTENANCE Note before cleaning and maintaining the machine...

Page 30: ...power button to switch off and unplug the unit 2 Drain the remaining water from the unit Clean the filter and let the filter dry completely in a shaded area 3 Collect the power cord at the water tank...

Page 31: ...available to hand Have a dry powder orCO2 fire extinguisher adjacent to the charging area 5 No ignition sources No person carrying out work in relation to a refrigeration system which involves exposin...

Page 32: ...ssive number of connections non compliance of terminals with the original specification damage to seals improper installation of oil seals etc Make sure that the device is installed in a secure manner...

Page 33: ...of the last charge of oxygen free nitrogen OFN the system shall be reset to atmospheric pressure to ensure its operability This operation is totally necessary before soldering on the pipelines Make s...

Page 34: ...rs shall be equipped with a pressure relief valve and corresponding shut off valves in proper working condition Empty cylinders shall be vacuumed and if possible cooled prior to the start of the cooli...

Page 35: ...ing Detailed information about the recycling of the device you can receive from a representative of the local authorities after providing full information about the device The manufacturer and authori...

Page 36: ...www hyundai home ru Manufactured Distributed by Home Electronics Limited China Licensed by Hyundai Corporation Holdings Korea Made in China...

Reviews: